Page 48 - Programmable Logic Controllers, Fifth Edition - Mobile version
P. 48

Analog input
                                                                                                modual
                                                                                                    1
                                        Temperature
                                          probe                                                     1C
                                                        Sensor                                      2
                                                      transducer  Transmitter                       2C
                                                                               0 to 10 V
                                                                               DC signal            3
                                                                                                    3C
                                                                                                    4
                                                                                10                  4C
                                                                           Volts
                                                                            DC
                                                                                 0
                                                                                    Time
                                        Figure 2-24  Analog input module circuit.

                                         Two-wire                        (ANL COM) points are electrically connected together
                                         transmitter                     inside the module but not to earth ground. When wiring
                                        Transmitter   Input module       single-ended analog input devices to the analog input
                                          +
                                              –
                         Power +                        IN+              card, the number of total wires necessary can be limited
                         supply –                       IN–
                                                        ANL COM          by using the ANALOG COMMON terminal, as shown
                                         Three-wire                      in Figure 2-26. Note that differential inputs are more
                                         transmitter                     immune to noise than single-ended inputs.
                                        Transmitter                        The  analog output interface module receives from
                                        supply signal  Input module
                         Power  +                       IN+              the processor digital data, which are converted into a
                         supply –          GND          IN–              proportional voltage or current to control an analog field
                                                        ANL COM
                                         Four-wire                       device. The transition of a digital signal to analog values
                                         transmitter                     is accomplished by a digital-to-analog (D/A) converter,
                                         Transmitter                     the main element of the analog output module. An analog
                                        supply signal  Input module
                         Power +         +     +        IN+              output signal is a continuous and changing signal that is
                         supply –        –     –        IN–              varied under the control of the PLC program. Common
                                                        ANL COM          devices controlled by a PLC analog output module in-
                                                                         clude instruments, control valves, chart recorder, elec-
                   Figure 2-25  Wiring two-, three-, and four-wire sensors to   tronic drives, and other types of control devices that
                   an analog input module.                               respond to analog signals. They employ standard analog
                                                                         output ranges such as ±5 V, ±10 V, 0 to 5 V, 0 to 10 V,
                     Power +           Transmitter                       4 to 20 mA, or 0 to 20 mA.
                                       +
                     supply –              signal           IN 0 +         Figure 2-27 illustrates the use of analog I/O modules
                                                            IN 0 –       in a typical PLC control system. In this application the
                                       Transmitter          ALL COM
                                       +   signal           IN 1 +
                                                            IN 1 –
                                                                                             Analog output
                                       Transmitter          ALL COM
                                       +
                                           signal           IN 2 +              Valve
                                                            IN 2 –
                                       Transmitter          ALL COM                             Level        PLC
                                     supply  signal                                             sensor
                                       +      +             IN 3 +
                                         Ground
                                                            IN 3 –
                                                            ALL COM                                  Analog input

                   Figure 2-26  Wiring single-ended analog input devices.  Figure 2-27  Typical analog I/O control system.



                                                                                 PLC Hardware Components  Chapter 2      29







          pet73842_ch02_017-045.indd   29                                                                               03/11/15   3:43 PM
   43   44   45   46   47   48   49   50   51   52   53