Page 9 - Multi Mfg Catalog 09-12-2020
P. 9
SPV‐HP Expanded Cooling Ratings
Cooling Performance Data (Sizes 25 ‐ 36)
Cooling Outdoor Conditions (DB)
Model Indoor Conditions 77F(25C) 86F(30C) 95F(35C) 104F(40C) 113F(45C) 122F(50C)
DB WB
TC 16.08 18.76 17.87 16.80 15.12 13.30
69.8 F (21 C) 59 F (15 C) SC 14.96 17.45 16.62 15.62 14.06 12.37
Input 1.54 1.97 1.92 1.96 1.90 1.86
TC 17.87 20.85 19.85 18.66 16.80 14.78
75.2 F (24 C) 62.6 F (17 C) SC 16.62 19.39 18.47 17.36 15.62 13.75
Input 1.57 2.01 1.96 2.00 1.94 1.90
25SPV
TC 23.82 23.16 22.06 21.80 19.62 16.87
80.6 F (27 C) 66.2 F (19 C) SC 21.96 21.55 20.52 19.14 17.23 14.81
Input 1.80 2.05 2.00 2.19 2.12 1.95
TC 25.48 24.99 24.27 22.81 20.53 18.07
89.6 F (32 C) 73.4 F (23 C) SC 23.70 23.25 22.57 21.22 19.10 16.80
Input 1.73 2.10 2.04 2.08 2.02 1.98
TC 19.90 23.22 22.11 20.79 18.71 16.46
69.8 F (21 C) 59 F (15 C) SC 14.96 17.45 16.62 15.62 14.06 12.37
Input 1.86 2.39 2.32 2.37 2.30 2.25
TC 22.11 25.80 24.57 23.10 20.79 18.29
75.2 F (24 C) 62.6 F (17 C) SC 16.62 19.39 18.47 17.36 15.62 13.75
Input 1.90 2.44 2.37 2.42 2.35 2.30
3036SPV
TC 29.48 28.67 27.30 25.10 22.59 19.43
80.6 F (27 C) 66.2 F (19 C) SC 21.96 21.55 20.52 21.00 18.90 16.25
Input 2.18 2.49 2.42 2.39 2.32 2.13
TC 31.53 30.93 30.03 28.23 25.41 22.36
89.6 F (32 C) 73.4 F (23 C) SC 23.70 23.25 22.57 21.22 19.10 16.80
Input 2.10 2.54 2.47 2.52 2.44 2.39
Legend
DB ‐ Dry Bulb
WB ‐ Wet Bulb
TC ‐ Total Net Cooling Capacity
SC ‐ Sensible Cooling Capacity
Input ‐ Total Power (kW)
Multi Manufacturing LLC 2480 Grand Ave., Vista, CA 92081 Ph 760‐670‐3005 Fax 760‐670‐3307 www.multimfg‐usa.com