Page 45 - DMcatalogue2017
P. 45
Low voltage AC drives
ABB general purpose drive
ACS580-01 – Dimensions and options
Dimensions and weights, wall-mounted drives
IP21 IP55
Frame Height Width Depth Weight Frame Height Width Depth Weight
size mm mm mm kg size mm mm mm kg
R0 303 125 210 4.5 R0 303 125 222 5.1
R1 303 125 223 4.6 H R1 303 125 233 5.1 H
R2 394 125 227 7.5 R2 394 125 239 8.0
R3 454 203 228 14.9 R3 454 203 237 15.4 4
R4 600 203 258 19 R4 600 203 265 20
R5 732 203 283 23 R5 732 203 320 29
R6 727 252 369 45 R6 726 252 380 45.5
R7 880 284 370 55 R7 880 284 381 55.5
R8 965 300 393 70 R8 965 300 452 72
D D
W W
IP21 IP55
Options for ACS580-01 Typical I/O connections for ACS580
ACS580-01 is a wall mounted drive, so all options These connections are shown as examples only. Please
fit inside: refer to the User’s Manual – macro section, for more detailed
– IP55 variant information and for different I/O configurations.
– Internal fieldbus options
– Optional additional industrial fieldbus X1 Meaning Default macro connections
– Optional relay expansion 1 2 SCR Signal cable shield (screen)
External frequency reference 1: 0 to 10 V
AI1
– Optional isolated PTC option 3 AGND Analogue input circuit common
4 +10V Output reference voltage 10 V DC
– Optional 115/230 V digital inputs 1 to 10 kohm 5 AI2 Analogueue input (not used)
– UK gland box to accommodate SWA cable 6 7 AGND Analogue input circuit common
Output frequency: 0 to 20 mA
AO1
– Brake chopper (up to frame R3 fitted as standard) 8 AO2 Output current: 0 to 20 mA
9 AGND Analogue output circuit common
Apart from IP55, the above also applies to ACS580-04 max. 500 ohm S3 AO1 I/U Voltage/Current selection for analogue output
and ACS580-07. X2 & X3 Aux. voltage output and programmable digital inputs
+24V
Auxiliary voltage output +24 V DC
10
11 DGND Auxiliary voltage output common
12 DCOM Digital input common for all DI
All ABB general purpose drives use the same common 13 DI1 Start/Stop: Activate to start
options and user interfaces. These are detailed on page 46. 14 DI2 Fwd/Rev: Activate to reverse rotation direction
15
DI3
Constant speed selection
They are also part of the “all compatible family” so keypad 16 DI4 Constant speed selection
17
DI5
Ramp pair selection: Activate to select
interfaces, common PC tools, parameter structures and second pair
18 DI6 Not used
programing methods are all common, even across other X6, X7, X8 Relay outputs
drive ranges. 19 RO1C Ready
20 RO1A 250 V AC/30 V DC
21 RO1B 2 A
22 RO2C Running
Cold configuration adapter – CCA-01 23 RO2A 250 V AC/30 V DC
ACS580 drives can be programmed without the need for 24 RO2B 2 A
RO3C
25
Fault (-1)
mains power or without taking the drive out of the box using 26 RO3A 250 V AC/30 V DC
27 RO3B 2 A
the CCA-01. This specifically allows rapid programming for X5 EIA-485 Modbus RTU
OEM without the need for safe areas in production. 29 B+
30 A- Built-in Modbus RTU fieldbus interface
31 DGND
S4 TERM Serial data link termination switch
S5 BIAS Serial data link bias resistors switch
X4 Safe torque-off
34 OUT1
35 OUT2
36 SGND Safe torque-off. Both circuits must be closed for the drive to start. The circuits are
closed with jumper wires in the standard delivery.
37 IN1
38 IN2
X10 24 V AC/DC*
40 24 V AC/DC-in. Ext. 24 V AC/DC input to power up the control unit when the main supply
is disconnected
41 24 V AC/DC+in.
*Standard on R6 frames and above and is optional on smaller frames
(requires a CMOD)
Drives and controls, motors and mechanical power transmission catalogue 45