Page 49 - DMcatalogue2017
P. 49

Low voltage AC drives

         ABB drive for HVAC

         ACH580-01 – Dimensions and options






         Dimensions and weights, wall-mounted drives

                        IP21                                                  IP55
         Frame   Height  Width  Depth  Weight                  Frame   Height  Width  Depth  Weight
         size    mm     mm    mm      kg                       size    mm     mm    mm      kg
         R0      303    125   210     4.5                      R0      303    125   222    5.1
         R1      303    125   223     4.6   H                  R1      303    125   233    5.1    H
         R2      394    125   227     7.5                      R2      394    125   239    8.0
         R3      454    203   228    14.9                      R3      454    203   237    15.4                      4
         R4      600    203   258     19                       R4      600    203   265     20
         R5      732    203   283     23                       R5      732    203   320     29
         R6      727    252   369     45                       R6      726    252   380    45.5
         R7      880    284   370     55                       R7      880    284   381    55.5
         R8      965    300   393     70                       R8      965    300   452     72
         R9      955    380   418     98       D               R9      955    380   477    100        D
                                                         W                                                     W
                                                    IP21                                                  IP55
         Options for ACH580-01                                 Typical I/O connections for ACH580
         ACH580-01 is a wall mounted drive, so all of the options    These connections are shown as examples only. Please
         fit inside:                                           refer to the User’s Manual – macro section, for more detailed
         – IP55 variant                                        information and for different I/O configurations.
         – Internal fieldbus options
         –  Optional additional industrial fieldbus                       X1  Meaning  Default connections
                                                                           1   SCR   Signal cable shield (screen)
         – Optional relay expansion                                        2   AI1   External frequency reference 1: 0 to 10 V
                                                                           3   AGND   Analogue input circuit common
         – Optional isolated PTC option                                    4   +10V   Output reference voltage 10 V DC
         – Optional 115/230 V digital inputs                   1 to 10 kohm  5   AI2   Analogueue input (not used)
                                                                           6   AGND   Analogue input circuit common
         – UK gland box to accommodate SWA cable                           7   AO1   Output frequency: 0 to 20 mA
                                                                           8   AO2   Output current: 0 to 20 mA
         – Brake chopper (up to frame R3 fitted as standard)               9   AGND   Analogue output circuit common
                                                               max. 500 ohm  S3   AO1 I/U   Voltage/Current selection for analogue output
                                                                         X2 & X3   Aux. voltage output and programmable digital inputs
         All ABB HVAC drives use the same common options and user          10   +24V   Auxiliary voltage output +24 V DC
                                                                           11   DGND   Auxiliary voltage output common
         interfaces. These are detailed on page 50. They are also part     12   DCOM   Digital input common for all DI
         of the “all compatible family” so keypad interfaces, common       13   DI1   Start/Stop: Activate to start
                                                                           14   DI2   Not configured
         PC tools, parameter structures and programing methods are         15   DI3   Constant speed selection
         all common.                                                       16   DI4   Not configured
                                                                           17
                                                                                  Not configured
                                                                               DI5
                                                                           18   DI6   Not configured
                                                                         X6, X7, X8  Relay outputs
         Cold configuration adapter – CCA-01                               19   RO1C                      Ready
         ACH580 drives can be programmed without the need for              20   RO1A                     250 V AC/30 V DC
                                                                                                      2 A
                                                                           21
                                                                               RO1B
         mains power or without taking the drive out of the box using      22   RO2C                     Running
                                                                                                      250 V AC/30 V DC
                                                                           23
                                                                               RO2A
         the CCA-01. This specifically allows rapid programming for        24   RO2B                     2 A
         OEM without the need for safe areas in production.                25   RO3C                     Fault (-1)
                                                                               RO3A
                                                                                                      250 V AC/30 V DC
                                                                           26
                                                                           27   RO3B                     2 A
                                                                          X5   EIA-485 Modbus RTU
                                                                           29   B+
                                                                           30   A-  Embedded modbus
                                                                           31   DGND
                                                                          S4   TERM  Serial data link termination switch
                                                                          S5   BIAS  Serial data link bias resistors switch
                                                                           X4   Safe torque-off
                                                                           34   OUT1
                                                                           35   OUT2
                                                                           36   SGND  Safe torque-off. Both circuits must be closed for the drive to start. The circuits are
                                                                                  closed with jumper wires in the standard delivery.
                                                                           37   IN1
                                                                           38   IN2
                                                                          X10  24 V AC/DC*
                                                                           40  24 V  AC/DC-in. Ext. 24 V AC/DC input to power up the control unit when the main supply
                                                                                  is disconnected
                                                                           41  24 V  AC/DC+in.
                                                                        *Standard on R6 frames and above and is optional on smaller frames
                                                                        (requires a CMOD)
                                                           Drives and controls, motors and mechanical power transmission catalogue  49
   44   45   46   47   48   49   50   51   52   53   54