Low voltage AC drives
ABB industrial drive
ACS880-07 – Variants, ratings, types, voltages and prices
Cabinet-built single drive
– 45 kW to 2,800 kW, (380 - 690 V)
– IP21 as standard, IP42 and IP54 as options
– 250 kW based on a single module including rectifier
and inverter
– Coated boards as standard
4 – TÜV approved safe torque-off (STO) to SIL 3 PL e standard
– TÜV approved emergency stopping options
– Extremely compact, internal swinging gate for control options
minimises cabinet size, but ensures easy access
– Internal customer wiring is redesigned to give easier access,
with pluggable connectors included
– Drive module can be extracted using a set of
maintenance rails
– Factory-built cabinet with EMC and thermally type-tested for
trouble-free operation
– Extensive range of standard options, that are increased to
incorporate the most popular engineered options ordered
with the ACS800 range
– Optional UK cable for SWA cables
– Optional motor thermistor and PTC connections
– Internal fieldbus options
– Optional safety module For further information, see Technical Catalogue 3AUA0000098111
– Optional I/O modules
– ATEX compliant options
380 to 415 V, 3-phase supply voltage. The power ratings are valid at nominal voltage (400 V)
No-overload Light-duty use Heavy-duty use Max output A Frame Fuse A Heat dissipation Cooling Type (+ E200, + R700 + Price
(nominal) use requirements H358 to order EMC &
† Type SWA gland plate)
P N I N P Ld I Ld P hd I hd
kW A kW A kW A aR W m /h
3
55 105 55 100 45 87 148 R6 160 1795 435 ACS880-07-0105A-3
75 145 75 138 55 105 178 R6 250 1940 435 ACS880-07-0145A-3
90 169 90 161 75 145 247 R7 250 2440 450 ACS880-07-0169A-3
110 206 110 196 90 169 287 R7 315 2810 450 ACS880-07-0206A-3
132 246 132 234 110 206 350 R8 400 3800 550 ACS880-07-0246A-3 application options. Price on range of standard ordered with a wide ABB panels can be
160 293 160 278 132 246* 418 R8 500 4400 550 ACS880-07-0293A-3
200 363 200 345 160 293 498 R9 630 5300 1150 ACS880-07-0363A-3
250 430 250 428 200 363** 545 R9 700 6500 1150 ACS880-07-0430A-3
*130% overload, **125% overload
† For fuse selection, refer to the hardware manual
ABB recommends the use of aR fuses for their cabinet drives, other fuses could be used if their melting
curve matches ABB’s recommendations