Page 124 - GuardII+ Series 4208 Platform PD User Manual
P. 124

Appendix



                        Each bit shown above may or may not be set, and the total value reported in the data
                     register is the sum of all of the ‘bit values’ of the set bits.
                        As an example, suppose the value reported for Measurement Status is 1025; from the bit
                     values shown in the table above, 1025 = 1 + 1024.  This would indicate that the “Data Ready”
                     and “Unstable AC Frequency” status bits are set.

                        Similarly, suppose the value reported for Measurement Status is 25; from the bit values
                     shown in the table above, 25 = 1 + 8 + 16.  This would indicate that the “Data Ready”, “Invalid
                     Qm” and “Over-Range” status bits are set.
                        Each bit has a meaning that provides context to the measurement.

                      Status Bit                 Meaning
                                                 When the GuardII+ is first powered up, it takes up to 65 minutes
                                                    to  run  a  full  set  of  PD  measurements  and  post  data  to
                                                    Modbus.
                      Data Ready                 The Data Ready bit is clear initially and becomes set when the
                                                    first measurement cycle is completed.
                                                 If Data Ready is not set, then there are no measurement results
                                                    completed yet.
                                                 If the System Error bit is set, then a system failure has occurred
                                                    in the monitor.
                      System Error               Refer to Section 7 for troubleshooting instructions and contact
                                                    Iris  Power  LP  Technical  Support  for  assistance  if
                                                    necessary.
                                                 If the Synchronization Error bit is set, then the GuardII+ cannot
                                                    detect a valid synchronization signal to run measurements.
                      Synchronization Error      Refer  to  Section  7.2.4  for  troubleshooting  instructions  and
                                                    contact Iris Power LP Technical Support for assistance if
                                                    necessary.
                                                 This bit is set when one or more of the Qm values could not be
                                                    calculated.  Note that there are 4 Qm values in a GuardII+
                                                    measurement, and the Invalid Qm bit will be set if any of the
                      Invalid Qm
                                                    Qm values cannot be calculated.
                                                 This typically occurs when the sensitivity being used needs to
                                                    be changed.
                                                 This bit is set when the PD data from the Asset or from the
                                                    System is higher than can be read on the current sensitivity.
                      Over Range
                                                 This  may  indicate  a  need  to  change  the  sensitivity  for  this
                                                    phase.
                                                 The  reference  frequency  was  not  stable  during  the
                      Unstable AC Frequency
                                                    measurement.
                                                 One  of  the  Qm  values  of  the  measurement  exceeded  the
                      Alert
                                                    configured Alert Thresholds.








                                                             116
                                                                                          www.irispower.com
   119   120   121   122   123   124   125   126   127   128