Page 117 - PBL614 IM/SM500F-EN SM500F ( WIRO)
P. 117

SM500F
Field mountable paperless recorder
7 Configuration
  7.9 Functions
Fig. 7.16 Functions Configuration
7.9.1 Custom Linearizers
Note.
 X is input to the linearizer expressed as a percentage of the electrical range.
 Y is output expressed as a percentage of the engineering range.
             Use the and
 Press the
Use the
Press the
Press the
keys to highlight the linearizer to be adjusted. key to open the 'Adjust custom linearizer' screen.
, , and keys to highlight the point to be modified. key to open the digipad to change the position of that point. key to return to the Functions screen.
           Each linearizer has 20 breakpoints. Both X and Y values are set as
percentages.
Custom linearizers can be applied to any analog input by selecting them as the linearizer type for that input – see 'Linearizer Type', page 96.
 IM/SM500F Rev. AA 115