Page 23 - puget sound energy community energy programs
P. 23

Chapter 1


              Figure 5           Minimum clearances from oil-filled equipment to LP, hazardous liquid, or fuel tanks



                                            6'
                                           MIN                                                         OIL-FILLED
                                                                                                       ELECTRICAL
                                                                              20'                      EQUIPMENT
                                                                              MIN                      (PAD OR POLE
                                                                                                       MOUNTED)
                                                     LP TANK





                                                   LP TANK
                                                                                                OIL-FILLED
                                                                                                ELECTRICAL
                                                                                                EQUIPMENT
                                                                                                (PAD OR POLE
                                                                                                MOUNTED)
                                                                           10'
                                                                           MIN
                                                                                     DIKE OF ADEQUATE HEIGHT TO
                                                                                     CONTAIN OIL AND NOT ALLOW IT
                                                                                     TO FLOW TOWARDS THE LP TANK
                                                  TOP VIEW


               Liquefied propane tanks: clearances from ignition source

                                 If there are liquefied propane (LP), hazardous liquid, or fuel tanks on your property, the
                                 following minimum clearances apply from PSE’s padmounted transformer or the ignition
                                 source (see Figures 5 and 6).
                                 •   All LP tanks must be at least 6 feet from a vertical plane extending down from an
                                     overhead primary voltage line.
                                 •   Consumer storage LP tanks must be at least 5 feet from any source of ignition,
                                     such as electric meter bases, submersible transformers, secondary handholes or
                                     pedestals, or padmount switches.
                                 •   The fill connection, gauge connection, or vent on the LP tank must be at least
                                     10 feet from any source of ignition.
               Figure 6          Minimum clearances from LP storage tanks to sources of ignition


                                                         PRIMARY VOLTAGE
                                                         POWER LINE



                                                                                ELECTRIC METER
                                                                                BASE OR SWITCH
                                                         GAUGE, VENT, OR
                                                        FILL CONNECTIONS


                                                        6' MIN            10' MIN
                                                        5' MIN
                                                                             5' MIN
                                                                  LP GAS


                                                      SUBMERSIBLE TRANSFORMER, HANDHOLE, SWITCH, OR PEDESTAL

               Electric Service Handbook 2017 — Single-Family Residential Projects                          14