Page 45 - puget sound energy community energy programs
P. 45
Chapter 3
Figure 21 Permanent overhead meter pole installation
OVERHEAD TO UNDERGROUND OVERHEAD TO OVERHEAD
UTILITY-OWNED CUSTOMER-OWNED UTILITY-OWNED CUSTOMER-OWNED
AND INSTALLED AND INSTALLED AND INSTALLED AND INSTALLED
8
8
1 1
POINT OF POINT OF
POINT OF ATTACHMENT POINT OF ATTACHMENT
DELIVERY 7 DELIVERY 7
6 6
OVERHEAD SERVICE
LOAD IF APPLICABLE
5
9 9 5
2 2
6' MAX 6' MAX
5' PREFERRED 5' PREFERRED
4' MIN 3 4' MIN 3
10% OF POLE 10% OF POLE 4
LENGTH, +2' 4 LENGTH, +2'
ANCHOR ROD * ANCHOR ROD *
* ANCHORS SHOULD BE EITHER SCREW TYPE OR CROSS-PLATE TYPE.
Items owned and installed by customer Items owned and installed by PSE
1 Customer-owned meter pole 8 Service line
2 Meter socket 9 Meter
3 Ground wire, in accordance with NEC/WAC
4 Ground rod(s), in accordance with NEC/WAC
Down guy, 5/16" minimum diameter
noncorrosive stranded steel wire required
5 for services over 70 ft from PSE pole. Push
brace or pole key brace may be substituted
for down guy.
6 Service entrance conductors - 18" out of
weatherhead
7 Insulated clevis
Electric Service Handbook 2017 — Single-Family Residential Projects 36