CONSTRUCT





       C1 Shopfront and BWIC






        C1.5 DT Signage Studs

        Where  new signage is proposed to drive thru          Where  no  existing studs can  be reused,  new
        buildings,  roof studs will  invariably  require      signage studs must be procured  as one  of
        alterations to accommodate.                           the standard engineer  details attached and
                                                              appropriately  fixed  to  the  roof  structure.  The
        The existing roof finish must be carefully stripped   attached is a typical  drawing for a standard
        back locally to allow stud fixing and allow new       Britspace / Yorkon modular building. For other
        signage electrical supplies to  be pulled into        variations the principal contractor must adapt
        position. The new / reused signage studs must         this detail to suit. Any further design work required
        be fixed as one of the standard engineer details      for site specific details will be undertaken by the
        attached and the roof weathered locally back          principal contractor. All new exposed steelwork
        to the roof finish.                                   must  be  constructed  with  a  galvanised  finish.
                                                              Any  mild steel (only acceptable below roof
                                                              finish line) must be finished with min 2No coats
                                                              red oxide paint finish.

                                                              Once the studs are correctly located and fixed
                                                              into  position,  the  existing  roof  finish  must  be
                                                              reinstated  around  the  studs and  adequately
                                                              weathered.   Signage stud location to be
                                                              coordinated with signage supplier.








































        C1.5           DT Signage Studs                     1.0                        08 October 2014