Page 52 - معین زیست آریا
P. 52
امرفراک
هناماس يزادنا هار و بصن ،تخاس ،هیهت ،یحارط
رتم رازه تسیب تیفرظ اب هتسب نک کنخ جرب
تعاس رد بعکم
DESIGN, PROCUREMENT,
CONSTRUCTION,
INSTALLATION AND
COMMISSIONING OF CLOSED
COOLING TOWER SYSTEM
WITH A COOLING WATER
CAPACITY OF 20,000 ⁄
CCT-20
DOCUMENT TITLE: REV:00 SHEET:
EQUIPMENT DOCUMENT NUMBER: Page 14 of 22
SPECIFICATION 60-06-DSH-ME-0002
TAG NO. 60-P-06-10 DESCRIPTION. DESUPERHEATING WATER
PUMP
PUMP TYPE: CENTRIF. (HORIZ.) CENTRIF. (VERT.) CENTRIF. (SUBMERSIBLE ROTARY
ETERING (DIAPHRAGM TYPE METERING (PISTON TYPE ECCENTRIC SCREW
NUMBER OF PUMPS REQUIRED: OPERATING: 1 SPARE: 0
TYPE OF DRIVER: ELECT. MOTOR: OPERATING: 1 SPARE: 0
DUTY CONTIN INTERMITT @APROXX HRS/YR
PROCESS REQUIREMENTS PER PUMP
OPERATING CASE REQUIRED FLOW CASE MAXIMUM MINIMUM
FLOW CASE FLOW CASE
LIQUIDE water
PUMPING TEMP. NORMAL o C 30 80
EXPECTED (MAX.) o C 80
SPGR @ P, T: 80/100 ºC RATED (MIN) 0.995 0.971
VAPOR PRESS. @ P, T: 60-100 ºC bar 0.0426 0.4739
VISCOSITY @ P, T: 80-100 ºC Cp 0.797 0.354
CAPACITY @ P, T: 80-100 ºC DESIGN m3/hr 30
NORM. m3/hr 30
DICH. PRESS. bar ( ga) 3 bar
SUCH. PRESS. (NORM.) bar ( ga) 1 bar
MAX. bar ( ga (
DIFFERENTIAL PRESS.: bar 2
DIFF. HEAD (CENTRIF. PUMPS ONLY) m 20
@100 ºC
NPSH AVAILABLE m 3-4
CORROSION/EROSION FROM
SPECIAL DETAILS
METHOD OF STARTING SPARE PUMP: MANUAL AUTOMATIC
NOTE.
MATERIALS RECOMMENDED: CASING: SST 304 IMPLLER: SST304