Page 344 - Installation Training Binder FIT1-3
P. 344
Step 7b
Installing Without Floor Anchors (Adhesive Method)
Make sure floor is clear of any debris. Adhesive/sealant should be applied
as Barrier Walls are assembled. Apply a ½” bead of acid-resistant
adhesive/sealant to the bottom of each piece; use the putty knife to spread
an even coat of adhesive/sealant over the entire bottom surface of each
Barrier Wall as they are put into place (Figure 9). A small amount of water
may be used to help smooth the adhesive/sealant and enhance the bead
of the seal. Allow adhesive/sealant to set.
Figure 9
Step 8
Final Assembly
Place the Extrusion Clips over the top of the Barrier Wall securing the liner
to the wall. In the event that height of the liner exceeds the Barrier Walls,
trim the liner as necessary after liner has been pushed fully into
containment. Continue installing the extrusion clips over Barrier Walls and
liner (Figure 10). CAUTION: Do NOT use the Barrier Wall as a guide
when trimming.
Step 9
Installing Neutralizing Pillows
Install pillows inside the floor of the liner. Spread pillows out to cover the
maximum amount of space. Place serial numbers facing up and in the
same direction whenever possible. Please note that the rack stanchions
may interfere with uniform pillow layout. (Figure 10)
Figure 10
EnviroGuard 800-206-9884 Fax 909-624-1772 www.egsintl.com
11/2007 rev. B Condor Plus System Setup Instructions Page - 9 -