Page 391 - Med Plaza and Cancer Center
P. 391

Corporation
                    Corporation




                                                                                     Appendix F





                    Wiring Schematic Heater Units








                                  Heater                  Heater                   Heater
                              Cartridge Wires         Terminal Block          Cartridge Wires










                                                                                               Reset-Switch



        Input                                                                                               Input
        Pressure                                                                                            Pressure


















        The Heaters are wired to our main Power Supply.  If the facility requires a separate circuit breaker for the Heaters, separate
        wires are required to be connected to the heater terminal block and the existing wiring from the heater terminal block
        to the power supply should be removed.

        The Heaters normally switch on when the temperature drops below 24°C or 75°F.  If the temperature exceeds 65-75°C or
        160-175°F, the Heater re-set switch will trip and the heaters will automatically switch off. To re-set the Heaters, remove
        the heater covers & press the red button on the re-set switch to activate. When the Heaters are in use or switched on, it
        will draw up to 3 amps of current.  The Heater Cartridge is 200Watts (each side), normally both sides do not switch on
        together. It depends on the flow of gas or climatic conditions. Heaters are available in 120V & 240V.






        PAGE   38


                  C                  US LISTED
   386   387   388   389   390   391   392   393   394   395   396