Installation & Dimensions
WALL OUTLETS
DISS, Ohmeda compatible, Chemetron compatible, Puritan-Bennett and Oxequip/MedStar compatible
Inch
[mm]
1 7/8” Wall thickness
When wall outlets are [48] may vary from
3/8" to 1"
ganged together, ensure [ 10mm to 25mm]
that they are 5” from center
to center. DO NOT let the 3/8”
[10]
notches on the mounting 5” 5” 5”
[127] [127] [127]
plate pass the adjacent holes
on the next mounting plate.
1/2" [12.7 mm] O.D. (3/8” nominal) type "K"
copper pipe, rotates 360 deg.
for entry from any angle
1-1/16”
[27]
YGEN OXYGEN
10”
[254]
5-3/4”
Do not bury the outlet during [146] 5-1/2”
5” [140]
the drywall and plaster [127]
OXY OXY
application. Ensure that the
cover over the outlet is in
place until the “Latch-valve
assembly” can be installed. 3” [76] NOTE:
Amico recomends that you have a blank space
5-27/32” [148] between outlets and slides.
Maximum 3 outlets may be ganged together
without additional support.