Page 144 - Select Specialty
P. 144
Oil-Less Claw Medical Vacuum
Appendix B: Variable Speed Drive Inverter
B.2.2 Parameter List (continued)
Minimum
Setting Initial Factory
Function Parameters Name Setting Range Increments Value Setting
Second acceleration/
44 0 to 3600/360s 0.1/0.01s 5s
deceleration time
45 Second deceleration time 0 to 3600/360s, 9999 0.1/0.01s 9999
46
0.1%
uctuations 47 Second torque boost 0 to 30%, 9999 0.01Hz 9999
0 to 400Hz, 9999
Second V/F (base frequency)
9999
Second stall prevention
0.1%
Second fl 48 operation current 0 to 120% 0.01Hz 110%
Second stall prevention
49
0 to 400Hz, 9999
0Hz
operationfrequency
Second output frequency
50 0 to 400Hz 0.01Hz 30Hz
detection
Second electronic thermal O/L 0 to 500A, 9999/0 to
51 0.01/0.1A 9999
relay 3600A, 9999
0, 5, 6, 8 to 14, 17,
DU/PU main display data
52 20, 23 to 25, 50 to 57, 1 0
selection 100
Monitor functions 54 CA terminal function selection 1 to 3, 5, 6, 8 to 14, 0.01Hz 60Hz 133.3
1
1
17, 21, 24, 50, 52, 53
55
Frequency monitoring reference 0 to 400Hz
Rated
56 Current monitoring reference 0 to 500A/0 to 3600A 0.01/0.1A inverter
output
current
Automatic resart functions 57 Restart coasting time 0, 0.1 to 5s, 9999/ 0, 0.1s 9999
0.1 to 30s, 9999
58
1s
0.1s
0 to 60s
Restart cushion time
---- 59 Remote function selection 0, 1, 2, 3 1 0
---- 60 Energy saving control selection 0, 4, 9 1 0
---- 65 Retry selection 0 to 5 1 0
Stall prevention operation
---- 66 0 to 400Hz 0.01Hz 60Hz
reduction starting frequency
Number of retries at alarm
67 0 to 10, 101 to 110 1 0
occurrence
Retry 68 Retry waiting time 0 to 10s 0.1s 1s
69 Retry count display erase 0 1 0
B-5 4107 9000 95.04