"Oil-Less” Scroll Medical Air                                                       Medical Systems


               3.0 System Operation (continued)



               3.1 Prestart-up (continued)

                                                              ®
               Verify electrical service. Before starting the LifeLine  Scroll Medical Air system, check to see that voltage,
               amperage, and wire size are appropriate.

               CAUTION: Electrical service must be as specified or damage to equipment may occur.


                                                         WARNING:
                    To prevent electrical shock, ensure that ALL electrical power to the system is OFF, including the
                   disconnect switches and H-O-A switches on the control panel.  The facility’s supply circuit breaker
                                                   should also be locked out.

               Open the electrical cabinet by loosening the fasteners on the front.

               CAUTION: Vibration during shipment and installation can loosen electrical terminals,  fuse  inserts,  and
               mechanical connections. Tighten as necessary.

               Check the electrical cabinet for any broken switches, lights, etc.

               Check that all motor starter connections are tight and that there are no loose objects such as terminal lugs,
               screws, nuts, etc., in the cabinet.