Page 33 - Select Specialty
P. 33

"Oil-Less” Scroll Medical Air                                                       Medical Systems


               3.0 System Operation (continued)



               3.4 Normal Operation (continued)

               3.4.2 Dryers

               This fully automatic, heat-less type  dryer  alternately cycles the compressed process gas flow through two
               desiccant charged vessels where the gas’  vaporous  moisture content is adsorbed. One desiccant vessel is
               always on-line in a  drying cycle  throughout normal dryer operation. The opposite, off-line vessel is in a
               regeneration cycle for removal of the previously adsorbed moisture content, or in a purge saving cycle at line
               pressure.

               When the dryer selector switch is in the “continuous purge” position, the dryer will shift towers every 30
               seconds. At normal operating conditions, one tower is approximately 110 psig and the other tower is at 0 psig.
               Any condition other than this is not normal and will cause a high dew point condition. During  tower
               changeover, the online chamber will exhaust, and the chamber that is regenerating (purging) will come to line
               pressure. There is no repressurization cycle. If the selector switch is on the continuous purge cycle, the dryer
               will use 15% of the system capacity to purge the dryer.

               When the dryer selector switch is in the “controlled purge” position, the dryer purge is controlled by the dew
               point monitor and purging depends on the dew point condition. When the dew point reading is above the
               setpoint of -10°C, the dryer will function normally (one tower at 110 psig, one tower at 0 psig). When the dew
               point is below the setpoint of -10° C on the dew point monitor, closing the exhaust valve turns off purge. In
               this condition, both towers will be approximately 110  psig and the dryer will  continue  to  shift  towers.
               However, the off line chamber will remain at 110 psig until the dew point is above -10°C.

               3.5 Normal Shutdown

               H-O-A switches-OFF

               Disconnect switches-OFF

               Main power source-OFF

               Hospital shutoff valve-CLOSED

               Air receiver manual tank drain-OPEN

               Pressure gauge decreasing to 0 psi (0 kPa)

               Close air receiver manual tank drain when pressure decreases to 0 psi (0 kPa)













                                                             3-7
   28   29   30   31   32   33   34   35   36   37   38