Page 34 - Select Specialty
P. 34

"Oil-Less” Scroll Medical Air                                                       Medical Systems


               3.0 System Operation (continued)



               3.6 Emergency Shutdown / Alarms

               The following conditions may arise during operation.

               High Air Temperature Shutdown - This will shut down the compressor in question and will not re-start until
               the appropriate red push button is pressed on the main control panel. Before allowing the unit to re-start, the
               condition should be checked (see “Compressor runs  hot” in the Troubleshooting Section 4.0). Even after
               pushing the button, the unit may not re-start, depending on system sequencing and system pressure.

               Motor Overload Shutdown - This will shut down the compressor in question and will not re-start until the
               reset button on the starter inside the main control cabinet is reset. See “Motor overheating” in  the
               Troubleshooting Section 4.0.

               Lag Unit Running Alarm - This alarm will activate if the last available compressor unit comes on.  In the
               case of a duplex system, it will activate when the second compressor turns on or the lag pressure switch (PS-2)
               closes. To silence the alarm, press the amber push button.  In the event the lag alarm is persistent, check to see
               if any leaks or valves are open downstream or reduce the system load.

               Dryer Tower Switching Failure Alarm (Optional) - For units with this feature, there is one pressure switch
               that senses pressure inside each dryer tower for a total of four pressure switches. If the pressure in both towers
               of the same dryer fall below 50 psig, the “dryer fault” light will come on and the remote dryer switching
               failure contacts will change condition (refer to the wiring  diagram  that  came with the unit for terminal
               numbers).  A short time delay (1.5  seconds)  is  started when both pressure switches fall below 50 psig to
               eliminate false alarms during normal tower switching.  To eliminate alarms during periods when the dryer is
               turned “off” for maintenance or other reasons, the dryer tower switching failure alarm is bypassed for that
               dryer.  Please note there is only one set of remote alarm contacts that will be activated in the event that either
               dryer has an alarm condition.

               Low Dryer Outlet Pressure Alarm (Optional) - For units with this feature, there is an adjustable pressure
               switch located upstream of the dryer check valve that will alarm if the pressure in that line drops below the 75
               psig factory setpoint.  In the event of an alarm, the “dryer fault” light will come on and a remote set of contacts
               will change condition (refer to the wiring diagram that came with the unit for terminal numbers).



























                                                             3-8
   29   30   31   32   33   34   35   36   37   38   39