Page 288 - 2018_IFC
P. 288

MOTOR FUEL-DISPENSING FACILITIES AND REPAIR GARAGES



                    dispenser at the point at which the dispenser hose is           SECTION 2308
                    connected to the liquid piping.                     COMPRESSED NATURAL GAS MOTOR
                                                                            FUEL-DISPENSING FACILITIES
                  4. A  listed automatic-closing type hose nozzle valve
                    with or without a latch-open device  shall be pro-  2308.1 General.  Motor fuel-dispensing facilities  for com-
                    vided on island-type dispensers.              pressed natural gas (CNG) fuel shall be in accordance with
                                                                  this section and Chapter 53.
               2307.6.2 Hoses. Hoses and piping for the dispensing of
               LP-gas shall  be  provided with hydrostatic relief valves.  2308.2 Approvals. Storage vessels and equipment used for
               The hose length shall not exceed 18 feet (5486 mm). An  the storage, compression or  dispensing of CNG shall be
               approved method shall be  provided  to protect the hose  approved or listed in accordance with Sections 2308.2.1 and
               against mechanical damage.                         2308.2.2.
                                                                     2308.2.1 Approved equipment. Containers, compressors,
               2307.6.3 Emergency breakaway devices. Dispenser
               hoses shall be equipped with a  listed emergency break-  pressure relief devices (including pressure relief valves),
               away device designed to retain liquid on both sides of the  and pressure regulators and piping used for CNG shall be
               breakaway  point. Where hoses are attached to hose-   approved.
               retrieving mechanisms, the emergency breakaway device  2308.2.2 Listed equipment. Hoses, hose connections, dis-
               shall be located such that the breakaway device activates  pensers and electrical equipment used for CNG shall be
               to protect the dispenser from being displaced.        listed.  Vehicle-fueling connections shall be  listed and
                                                                     labeled.
               2307.6.4  Vehicle impact protection. Where installed
               within 10 feet of vehicle traffic, LP-gas storage containers,  2308.3 Location of dispensing operations and equipment.
               pumps and  dispensers shall  be  protected in accordance  Compression, storage and dispensing  equipment  shall  be
               with Section 2307.5, Item 2.                       located above ground, outdoors.
                                                                     Exceptions:
             2307.7 Public fueling of  motor  vehicles.  Self-service LP-
             gas  dispensing  systems, including key, code and card lock  1. Compression, storage or dispensing equipment shall
             dispensing systems, shall be limited to the filling of perma-  be allowed in buildings of noncombustible construc-
             nently mounted containers providing fuel to the LP-gas pow-  tion, as set forth in the International Building Code,
             ered vehicle.                                               that are unenclosed for three-quarters or more of the
                                                                         perimeter.
               The requirements for self-service LP-gas dispensing sys-
             tems shall be in accordance with the following:           2. Compression, storage and dispensing equipment
                                                                         shall be allowed indoors or in vaults in accordance
               1. The arrangement and operation of the transfer of prod-  with Chapter 53.
                  uct into a vehicle shall be in accordance with this sec-  2308.3.1 Location on property. In addition to the
                  tion and Chapter 61.
                                                                     requirements of Section 2303.1, compression, storage and
               2. The system shall be provided with an emergency shut-  dispensing equipment not located in vaults complying
                  off switch located within 100 feet (30 480 mm) of, but  with Chapter 53 shall be installed as follows:
                  not less than 20 feet (6096 mm) from, dispensers.    1. Not beneath power lines.
               3. The owner of the LP-gas motor fuel-dispensing facility  2. Ten feet (3048 mm) or more from the nearest build-
                  or the owner’s designee shall provide for the safe oper-  ing or lot line that could be built on, public street,
                  ation of the system and the training of users.         sidewalk or source of ignition.
               4. The dispenser and hose-end valve shall  release not       Exception: Dispensing  equipment  need not be
                           1
                  more than  /  fluid ounce (4 cc) of liquid to the atmo-   separated from  canopies  that are constructed  in
                            8
                  sphere upon breaking the connection with the fill valve   accordance with the International Building Code
                  on the vehicle.                                           and that provide weather protection for the dis-
                                                                            pensing equipment.
               5. Portable fire extinguishers shall be provided in accor-
                  dance with Section 2305.5.                           3. Twenty-five feet (7620 mm) or more from the near-
                                                                         est rail of any railroad track and 50 feet (15 240 mm)
               6. Warning signs  shall be provided  in  accordance with  or more from the nearest rail of any railroad main
                  Section 2305.6.
                                                                         track or any railroad or transit line where power for
               7. The area around the dispenser shall be maintained in   train propulsion is provided by an outside electrical
                  accordance with Section 2305.7.                        source, such as third rail or overhead catenary.
                                                                       4. Fifty feet (15  240  mm) or more from the  vertical
             2307.8 Overfilling. LP-gas containers shall not be filled with
             LP-gas in excess of the volume determined using the fixed   plane below the nearest overhead wire of a trolley
             maximum liquid level gauge installed on the container, the  bus line.
             volume  determined by  the overfilling prevention device  2308.4 Private fueling of motor vehicles. Self-service
             installed on the container or the weight determined by the  CNG-dispensing systems, including key, code and card lock
             required percentage of the water capacity marked on the con-  dispensing systems, shall be limited to the filling of perma-
             tainer.                                              nently mounted fuel containers on CNG-powered vehicles.

             2018 INTERNATIONAL FIRE CODE ®                                                                      255
  Copyrighted © 2017 by, or licensed to, ICC (ALL RIGHTS RESERVED); licensed to UL, LLC pursuant to License Agreement with ICC. No further reproductions authorized or distribution authorized.
  ANY UNAUTHROIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT; AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
   283   284   285   286   287   288   289   290   291   292   293