FLAMMABLE FINISHES
2404.6.1.2.2 Portable infrared apparatus. Where 2404.7.2 Recirculation. Air exhausted from spraying
a portable infrared drying apparatus is used, electri- operations shall not be recirculated.
cal wiring and portable infrared drying equipment Exceptions:
shall comply with NFPA 70. Electrical equipment
located within 18 inches (457 mm) of floor level 1. Air exhausted from spraying operations is
shall be approved for Class I, Division 2 hazardous allowed to be recirculated as makeup air for
locations. Metallic parts of drying apparatus shall be unmanned spray operations, provided that all of
the following conditions exist:
electrically bonded and grounded. During spraying
operations, portable drying apparatus and electrical 1.1. The solid particulate has been removed.
connections and wiring thereto shall not be located 1.2. The vapor concentration is less than 25
within spray booths, spray rooms or other areas percent of the LFL.
where spray residue would be deposited thereon.
1.3. Approved equipment is used to monitor
2404.6.2 Illumination. Where spraying spaces, spray
rooms or spray booths are illuminated through glass panels the vapor concentration.
or other transparent materials, only fixed luminaires shall 1.4. When the vapor concentration exceeds 25
be utilized as a source of illumination. percent of the LFL, both of the following
shall occur:
2404.6.2.1 Glass panels. Panels for luminaires or for
observation shall be of heat-treated glass, wired glass 1.4.1. An alarm shall sound.
or hammered wire glass and shall be sealed to confine 1.4.2. Spray operations shall automat-
vapors, mists, residues, dusts and deposits to the flam- ically shut down.
mable vapor area. Panels for luminaires shall be sepa- 1.5. In the event of shutdown of the vapor
rated from the luminaire to prevent the surface concentration monitor, 100 percent of the
temperature of the panel from exceeding 200°F (93°C).
air volume specified in Section 510 of the
2404.6.2.2 Exterior luminaires. Luminaires attached International Mechanical Code is auto-
to the walls or ceilings of a flammable vapor area, but matically exhausted.
outside of any classified area and separated from the 2. Air exhausted from spraying operations is
flammable vapor areas by vapor-tight glass panels, allowed to be recirculated as makeup air to
shall be suitable for use in ordinary hazard locations. manned spraying operations where all of the con-
Such luminaires shall be serviced from outside the ditions provided in Exception 1 are included in
flammable vapor areas.
the installation and documents have been pre-
2404.6.2.3 Integral luminaires. Luminaires that are an pared to show that the installation does not pose a
integral part of the walls or ceiling of a flammable life safety hazard to personnel inside the spray
vapor area are allowed to be separated from the flam- booth, spraying space or spray room.
mable vapor area by glass panels that are an integral 2404.7.3 Air velocity. The ventilation system shall be
part of the luminaire. Such luminaires shall be listed for designed, installed and maintained so that the flammable
use in Class I, Division 2 or Class II, Division 2 loca- contaminants are diluted in noncontaminated air to main-
tions, whichever is applicable, and shall be suitable for tain concentrations in the exhaust airflow below 25 per-
accumulations of deposits of combustible residues. cent of the contaminant’s lower flammable limit (LFL). In
Such luminaires are allowed to be serviced from inside addition, the spray booth shall be provided with mechani-
the flammable vapor area.
cal ventilation so that the average air velocity through
2404.6.2.4 Portable electric lamps. Portable electric openings is in accordance with Sections 2404.7.3.1 and
lamps shall not be used in flammable vapor areas 2404.7.3.2.
during spraying operations. Portable electric lamps 2404.7.3.1 Open-face or open-front spray booth. For
used during cleaning or repairing operations shall be of spray application operations conducted in an open-face
a type approved for hazardous locations.
or open-front spray booth, the ventilation system shall
2404.7 Ventilation. Mechanical ventilation of flammable be designed, installed and maintained so that the aver-
vapor areas shall be provided in accordance with Section age air velocity into the spray booth through all open-
502.7 of the International Mechanical Code. ings is not less than 100 feet per minute (0.51 m/s).
2404.7.1 Operation. Mechanical ventilation shall be kept Exception: For fixed or automated electrostatic
in operation at all times while spraying operations are spray application equipment, the average air veloc-
being conducted and for a sufficient time thereafter to ity into the spray booth through all openings shall be
allow vapors from drying coated articles and finishing not less than 50 feet per minute (0.25 m/s).
material residue to be exhausted. Spraying equipment
shall be interlocked with the ventilation of the flammable 2404.7.3.2 Enclosed spray booth or spray room with
vapor areas such that spraying operations cannot be con- openings for product conveyance. For spray applica-
ducted unless the ventilation system is in operation. tion operations conducted in an enclosed spray booth or
spray room with openings for product conveyance, the
2018 INTERNATIONAL FIRE CODE ® 267