FLAMMABLE FINISHES



                    2404.6.1.2.2 Portable infrared apparatus. Where  2404.7.2 Recirculation.  Air exhausted from  spraying
                    a portable infrared drying apparatus is used, electri-  operations shall not be recirculated.
                    cal wiring and portable infrared drying equipment  Exceptions:
                    shall comply  with NFPA  70. Electrical  equipment
                    located within 18 inches (457  mm) of  floor  level  1. Air  exhausted  from spraying operations is
                    shall be approved for Class I, Division 2 hazardous     allowed  to  be  recirculated as makeup air for
                    locations. Metallic parts of drying apparatus shall be  unmanned spray operations, provided that all of
                                                                            the following conditions exist:
                    electrically bonded and grounded. During spraying
                    operations, portable drying apparatus and electrical      1.1. The solid particulate has been removed.
                    connections and wiring thereto shall not be located       1.2. The vapor concentration is less than 25
                    within  spray booths,  spray rooms or  other areas            percent of the LFL.
                    where spray residue would be deposited thereon.
                                                                              1.3. Approved equipment is used  to monitor
               2404.6.2 Illumination.  Where  spraying spaces, spray
               rooms or spray booths are illuminated through glass panels         the vapor concentration.
               or other transparent materials, only fixed luminaires shall    1.4. When the vapor concentration exceeds 25
               be utilized as a source of illumination.                           percent of the LFL, both of the following
                                                                                  shall occur:
                  2404.6.2.1 Glass panels. Panels for luminaires or for
                  observation shall be of heat-treated glass, wired glass           1.4.1. An alarm shall sound.
                  or hammered wire glass and shall be sealed to confine             1.4.2. Spray operations shall automat-
                  vapors, mists, residues, dusts and deposits to the flam-                ically shut down.
                  mable vapor area. Panels for luminaires shall be sepa-      1.5. In  the event of shutdown  of  the vapor
                  rated from  the luminaire  to  prevent the surface              concentration monitor, 100 percent of the
                  temperature of the panel from exceeding 200°F (93°C).
                                                                                  air volume specified in Section 510 of the
                  2404.6.2.2 Exterior luminaires. Luminaires attached             International Mechanical Code is  auto-
                  to the walls or ceilings of a flammable vapor area, but         matically exhausted.
                  outside  of  any classified area  and separated from  the  2. Air  exhausted  from spraying operations is
                  flammable vapor  areas by vapor-tight  glass  panels,     allowed to be recirculated as makeup air to
                  shall be suitable for use in ordinary hazard locations.   manned spraying operations where all of the con-
                  Such luminaires shall be serviced from outside the        ditions provided in Exception 1 are included in
                  flammable vapor areas.
                                                                            the  installation and documents have  been pre-
                  2404.6.2.3 Integral luminaires. Luminaires that are an    pared to show that the installation does not pose a
                  integral part of the walls or ceiling of a flammable      life safety hazard  to personnel  inside the spray
                  vapor area are allowed to be separated from the flam-     booth, spraying space or spray room.
                  mable vapor area by glass panels that are an integral  2404.7.3 Air velocity. The ventilation system shall be
                  part of the luminaire. Such luminaires shall be listed for  designed, installed and maintained so that the flammable
                  use in Class I, Division 2 or Class II, Division 2 loca-  contaminants are diluted in noncontaminated air to main-
                  tions, whichever is applicable, and shall be suitable for  tain concentrations in the exhaust airflow below 25 per-
                  accumulations of  deposits of combustible residues.  cent of the contaminant’s lower flammable limit (LFL). In
                  Such luminaires are allowed to be serviced from inside  addition, the spray booth shall be provided with mechani-
                  the flammable vapor area.
                                                                     cal ventilation  so  that the  average air velocity  through
                  2404.6.2.4 Portable electric lamps.  Portable electric  openings is in  accordance with  Sections  2404.7.3.1 and
                  lamps shall not be used in  flammable vapor areas  2404.7.3.2.
                  during spraying operations. Portable electric  lamps  2404.7.3.1 Open-face or open-front spray booth. For
                  used during cleaning or repairing operations shall be of  spray application operations conducted in an open-face
                  a type approved for hazardous locations.
                                                                       or open-front spray booth, the ventilation system shall
             2404.7 Ventilation. Mechanical  ventilation of  flammable  be designed, installed and maintained so that the aver-
             vapor areas shall be  provided in accordance with Section  age air velocity into the spray booth through all open-
             502.7 of the International Mechanical Code.               ings is not less than 100 feet per minute (0.51 m/s).
               2404.7.1 Operation. Mechanical ventilation shall be kept  Exception: For fixed or automated electrostatic
               in  operation at all times  while spraying  operations  are  spray application equipment, the average air veloc-
               being conducted and for a sufficient time thereafter to   ity into the spray booth through all openings shall be
               allow vapors from  drying coated articles and finishing   not less than 50 feet per minute (0.25 m/s).
               material  residue to be exhausted.  Spraying equipment
               shall be interlocked with the ventilation of the flammable  2404.7.3.2 Enclosed spray booth or spray room with
               vapor areas such that spraying operations cannot be con-  openings for product conveyance. For spray applica-
               ducted unless the ventilation system is in operation.   tion operations conducted in an enclosed spray booth or
                                                                       spray room with openings for product conveyance, the