FLAMMABLE FINISHES



              ventilation system shall be  designed, installed and   feet (9144 mm) from combustible walls or openings
              maintained so  that the  average  air velocity into  the  into the building that are in the direction  of the
              spray booth through openings is not less than 100 feet  exhaust discharge; 10 feet (3048 mm) above adjoin-
              per minute (0.51 m/s).                                 ing grade.
                Exceptions:                                        2. Other product-conveying outlets: 10 feet (3048 mm)
                                                                     from the  lot line; 3 feet (914  mm)  from  exterior
                   1. For fixed or automated electrostatic spray
                                                                     walls and roofs; 10 feet (3048 mm) from openings
                     application equipment, the average air veloc-
                     ity into the spray booth through all openings   into the building; 10 feet (3048 mm) above adjoin-
                     shall be not less than 50 feet per minute (0.25  ing grade.
                     m/s).                                       2404.7.7 Fan motors and belts. Electric motors driving
                                                                 exhaust fans shall not  be  placed  inside booths  or ducts.
                   2. Where methods are used to reduce cross drafts
                     that can draw vapors  and  overspray  through  Fan rotating elements shall be nonferrous or nonsparking
                     openings from the spray booth or spray room,  or the casing shall consist of, or be lined with, such mate-
                     the average air velocity into the spray booth or  rial. Belts shall not enter the duct or booth unless the belt
                     spray room shall be that necessary to capture  and pulley within the duct are tightly enclosed.
                     and confine vapors and overspray to the spray  2404.7.8 Filters. Air intake filters that are part of a wall or
                     booth or spray room.                        ceiling assembly shall be listed as Class I or II in accor-
           2404.7.4 Ventilation obstruction. Articles being sprayed  dance with UL 900. Exhaust filters shall be required.
           shall be positioned in a manner that does not obstruct col-  2404.7.8.1 Supports. Supports and holders for filters
           lection of overspray.                                   shall be constructed of noncombustible materials.
           2404.7.5 Independent ducts. Each spray booth and spray  2404.7.8.2 Attachment. Overspray collection filters
           room shall have an independent exhaust duct system dis-  shall be readily removable and able to be accessed for
           charging to the outside.                                cleaning or replacement.
              Exceptions:                                          2404.7.8.3 Maintaining air velocity. Visible gauges,
                1. Multiple spray booths having a combined frontal  audible alarms or pressure-activated devices shall be
                                              2
                   area of 18 square feet (1.67 m ) or less are    installed to indicate or ensure that the required air
                   allowed to have a common exhaust where identi-  velocity is maintained.
                   cal spray finishing material is used in each booth.  2404.7.8.4 Filter rolls. Spray booths equipped with a
                   If more than one fan serves one booth, fans shall  filter roll that is automatically advanced when the air
                   be interconnected such that all fans will operate  velocity  is reduced to less than 100 feet per minute
                   simultaneously.                                 (0.51 m/s) shall be arranged to shut down the spraying
                2. Where treatment of exhaust is necessary for air  operation if the filter roll  fails to advance automati-
                   pollution control or for energy conservation,   cally.
                   ducts shall be allowed to be manifolded if all of  2404.7.8.5 Filter disposal. Discarded filter pads shall
                   the following conditions are met:               be immediately removed to a safe, detached location or
                     2.1. The sprayed materials used are compati-  placed in a noncombustible container with a tight-fit-
                         ble and will not react or cause ignition of  ting lid and disposed of properly.
                         the residue in the ducts.                 2404.7.8.6 Spontaneous ignition. Spray booths using
                     2.2. Nitrocellulose-based finishing material  dry filters shall not be used for spraying materials that
                         shall not be used.                        are highly susceptible to spontaneous heating and igni-
                                                                   tion. Filters shall be changed prior to spraying materials
                     2.3. A  filtering system shall be provided to  that could react with other materials previously col-
                         reduce  the amount of overspray carried   lected. An example of a potentially reactive combina-
                         into the duct manifold.
                                                                   tion includes lacquer when  combined with varnishes,
                     2.4. Automatic sprinkler protection shall be  stains or primers.
                         provided  at the junction of each  booth  2404.7.8.7 Waterwash  spray booths. Waterwash
                         exhaust with the manifold, in addition to  spray booths shall be of an approved design so as to
                         the protection required by this chapter.  prevent excessive accumulation of deposits  in ducts
           2404.7.6 Termination point. The termination point for   and residue  at  duct outlets. Such booths  shall be
           exhaust ducts discharging to the atmosphere shall be not  arranged so that air and overspray are drawn through a
           less than the following distances:                      continuously flowing water curtain before entering an
                                                                   exhaust duct to the building exterior.
              1. Ducts conveying explosive or flammable vapors,
                fumes or dusts: 30 feet (9144 mm) from the lot line;  2404.8 Interlocks. Interlocks  for spray  application finishes
                10 feet (3048 mm) from openings into the building;  shall  be  in  accordance with Sections 2404.8.1 through
                6 feet (1829 mm) from exterior walls and roofs; 30  2404.8.2.