P. 335
TENTS, TEMPORARY SPECIAL EVENT STRUCTURES AND OTHER MEMBRANE STRUCTURES
and the system shall be installed in accordance 3. Trade name or kind of chemical used in treatment.
with NFPA 70. The emergency system provided 4. Name of person or firm treating the material.
shall have a minimum duration of 90 minutes
when operated at full design demand. 5. Name of testing agency and test standard by which the
fabric was tested.
3103.12.7 Means of egress illumination. Means of egress *
shall be illuminated with light having an intensity of not
less than 1 foot-candle (11 lux) at floor level while the SECTION 3105
structure is occupied. Fixtures required for means of TEMPORARY SPECIAL EVENT STRUCTURES
egress illumination shall be supplied from a separate cir-
cuit or source of power. 3105.1 General. Temporary special event structures shall
comply with Section 3104, Sections 3105.2 through 3105.9
3103.12.8 Maintenance of means of egress. The required
width of exits, aisles and passageways shall be maintained and ANSI E1.21.
at all times to a public way. Guy wires, guy ropes and 3105.2 Approval. Temporary special event structures in
2
other support members shall not cross a means of egress at excess of 400 square feet (37 m ) shall not be erected, oper-
a height of less than 8 feet (2438 mm). The surface of ated or maintained for any purpose without first obtaining
means of egress shall be maintained in an approved man- approval and a permit from the fire code official and the
ner. building official.
3105.3 Permits. Permits shall be required as set forth in Sec-
tions 105.6 and 105.7.
SECTION 3104
TEMPORARY AND PERMANENT TENTS 3105.4 Use period. Temporary special event structures
AND MEMBRANE STRUCTURES erected in accordance with ANSI E1.21 shall not be erected
for a period of more than six consecutive weeks.
3104.1 General. Tents and membrane structures, both tem-
porary and permanent, shall be in accordance with this sec- 3105.5 Required documents. The following documents
tion and Sections 3106 and 3107. Permanent tents and shall be submitted to the fire code official and the building
membrane structures shall also comply with the International official for review before a permit is approved:
Building Code.
1. Construction documents: Construction documents shall
3104.2 Flame propagation performance treatment. Before be prepared by a registered design professional in
a permit is granted, the owner or agent shall file with the fire accordance with the International Building Code and
code official a certificate executed by an approved testing ANSI E1.21 where applicable. Construction documents
laboratory. The certificate shall indicate that the floor cover- shall include:
ings, tents, membrane structures and their appurtenances, 1.1. A summary sheet showing the building code
which include sidewalls, drops and tarpaulins, are composed used, design criteria, loads and support reac-
of materials meeting the flame propagation performance of tions.
Test Method 2 of NFPA 701. Additionally, it shall indicate
that the bunting and combustible decorative materials and 1.2. Detailed construction and installation drawings.
effects are composed of material meeting the flame propaga- 1.3. Design calculations.
tion performance criteria of Test Method 1 or Test Method 2 1.4. Operating limits of the structure explicitly out-
of NFPA 701, as applicable. Alternatively, the materials shall lined by the registered design professional
be treated with a flame retardant in an approved manner and including environmental conditions and physi-
meet the flame propagation performance criteria of the appli- cal forces.
cable test method of NFPA 701. The flame propagation per-
formance criteria shall be effective for the period specified by 1.5. Effects of additive elements such as video
the permit. walls, supported scenery, audio equipment, ver-
tical and horizontal coverings.
3104.3 Label. Membrane structures or tents shall have a per-
manently affixed label bearing the identification of size and 1.6. Means for adequate stability including specific
fabric or material type. requirements for guying and cross-bracing,
ground anchors or ballast for different ground
3104.4 Certification. An affidavit or affirmation shall be conditions.
submitted to the fire code official and a copy retained on the
premises on which the tent or air-supported structure is 2. Designation of responsible party: The owner of the
located. The affidavit shall attest to all of the following infor- temporary special event structure shall designate in
mation relative to the flame propagation performance criteria writing a person to have responsibility for the tempo-
of the fabric: rary special event structure on the site. The designated
person shall have sufficient knowledge of the construc-
1. Names and address of the owners of the tent or air-sup- tion documents, manufacturer’s recommendations and
ported structure.
operations plan to make judgments regarding the struc-
2. Date the fabric was last treated with flame-retardant ture’s safety and to coordinate with the fire code offi-
solution. cial.