CHAPTER 32

                                  HIGH-PILED COMBUSTIBLE STORAGE




             User note:
                About this chapter: Chapter 32 provides guidance for reasonable protection of life from hazards associated with the storage of combustible
                materials in closely packed piles or on pallets, in racks or on shelves where the top of storage is greater than 12 feet in height, or 6 feet for
                high-hazard commodities. It provides requirements for identifying various classes of commodities; and general fire and life safety features
                including storage arrangements, smoke and heat venting, fire department access and housekeeping and maintenance. This chapter attempts
                to define the potential fire severity and, in turn, determine fire and life safety protection measures needed to control and in some cases sup-
                press a potential fire. This chapter does not cover miscellaneous combustible material storage as regulated in Section 315.



                               SECTION 3201                           8. Location of commodities that are banded or encapsu-
                                 GENERAL                                lated.
             3201.1 Scope.  High-piled combustible storage shall be  in  9. Location of required fire department access doors.
             accordance with this chapter. In addition to the requirements  10. Type of fire suppression and fire detection systems.
             of this chapter, the following material-specific requirements
             shall apply:                                            11. Location  of  valves controlling the water  supply of
                                                                        ceiling and in-rack sprinklers.
               1. Aerosols shall be in accordance with Chapter 51.
                                                                     12. Type, location  and  specifications of smoke removal
               2. Flammable and combustible liquids shall be in accor-  and curtain board systems.
                  dance with Chapter 57.
                                                                     13. Dimension and location of transverse and longitudinal
               3. Hazardous materials shall be in accordance with Chap-  flue spaces.
                  ter 50.
                                                                     14. Additional information regarding required design fea-
               4. Storage of combustible paper records shall be in accor-  tures, commodities, storage arrangement and fire pro-
                  dance with NFPA 13.                                   tection features  within the  high-piled storage  area
               5. Storage of  combustible fibers shall be in accordance  shall be provided at the time of permit, where required
                  with Chapter 37.                                      by the fire code official.
               6. General storage of combustible  material shall  be  in  3201.3.1 Approved construction documents. Following
                  accordance with Chapter 3.                         approval of the  construction documents, a  copy of the
             3201.2 Permits. A  permit shall  be  required  as set forth in  approved plans shall be maintained on the premises in an
             Sections 105.6 and 105.7.                               approved location.
             3201.3 Construction  documents. At  the  time of building  3201.3.2 Approved storage layout. A floor plan, of legi-
             permit application for new structures designed to accommo-  ble size, shall be provided, mounted on a wall and pro-
             date high-piled storage or for requesting a change of occu-  tected from damage. The floor plan shall be mounted in an
             pancy/use, and at the time of application for a storage permit,  approved location and show the following:
             plans and  specifications  shall be submitted for review and  1. Locations, dimensions and rack layout of high-piled
             approval. In addition to the information required by the Inter-  storage areas.
             national Building  Code, the storage permit  submittal shall  2. Design storage height for each storage area.
             include the information specified in this section. The  con-
             struction documents shall include all of the following:   3. Types of commodities.
                                                                       4. Commodity  clearance between top  of storage and
                1. Floor  plan of the building showing locations and
                   dimensions of high-piled storage areas.               the sprinkler deflector for each storage arrangement.
                                                                       5. Aisle dimensions between each storage array.
                2. Usable storage height for each storage area.
                                                                       6. For palletized and solid-piled storage, the maximum
                3. Number of tiers within each rack, if applicable.
                                                                         pile volume for each storage array.
                4. Commodity clearance between top of storage and the
                   sprinkler deflector for each storage arrangement.   7. Location and classification of commodities in accor-
                                                                         dance with Section 3203.
                5. Aisle dimensions between each storage array.
                                                                       8. Location of required fire department access doors.
                6. Maximum pile volume for each storage array.
                                                                       9. Location of valves controlling the water supply of
                7. Location and classification of commodities in accor-  ceiling and in-rack sprinklers.
                   dance with Section 3203.