HIGH-PILED COMBUSTIBLE STORAGE



           be considered fire  department access doors unless           2. Aisles  that are in  high-piled storage  areas
                                                                                                       2
           approved.                                                      exceeding 2,500 square feet (232 m ) in area,
           3206.7.7 Locking  devices. Locking devices on fire             not open  to the  public and protected  by  a
           department access doors shall be approved.                     sprinkler system designed  for  multiple-row
                                                                          racks,  shall  be not less than 24 inches  (610
           3206.7.8 Key box. Where fire department access doors are       mm) wide.
           required, a key box shall be installed in accordance with
           Section 506.1. The key box shall contain keys or devices  3206.10.1.2 Nonsprinklered buildings. Aisles in non-
           to allow for entry through the fire department access   sprinklered buildings shall be not less than 96 inches
           doors.                                                  (2438 mm) wide.
         3206.8 Smoke and  heat  removal. Where smoke and  heat  3206.10.2 Clear  height.  The  required aisle width shall
         removal is required by Table 3206.2 it shall be provided in  extend from floor to ceiling. Rack structural supports and
         accordance with Section 910.                            catwalks are allowed to cross aisles at a minimum height
                                                                 of  6 feet 8  inches (2032 mm) above the finished  floor
         3206.9 Fire department hose connections. Where exit pas-  level, provided that such supports do not interfere with fire
         sageways are required by the International Building Code for  department hose stream trajectory.
         egress, a Class I standpipe system shall be provided in accor-
         dance with Section 905.                                 3206.10.3 Dead-end aisles. Dead-end  aisles shall not
                                                                 exceed 20 feet (6096 mm) in length in Group M occupan-
         3206.10 Aisles. Aisles providing access to  exits and fire  cies. Dead-end aisles shall not exceed 50 feet (15 240 mm)
         department access doors shall be provided in high-piled stor-  in length in all other occupancies.
                                             2
         age areas exceeding 500 square feet (46 m ), in accordance
         with Sections 3206.10.1 through 3206.10.3. Aisles separating  Exception: Dead-end aisles are not limited where the
         storage piles or racks shall  comply  with NFPA 13.  Aisles  length of the dead-end aisle is less than 2.5 times the
         shall comply with Chapter 10.                             least width of the dead-end aisle.
           Exception: Where  aisles are precluded  by  rack storage  3206.11 Portable fire  extinguishers. Portable  fire extin-
           systems, alternate methods of  access and  protection  are  guishers shall be provided in accordance with Section 906.
           allowed where approved.
           3206.10.1 Width. Aisle width shall be in accordance with             SECTION 3207
           Sections 3206.10.1.1 and 3206.10.1.2.                     SOLID-PILED AND SHELF STORAGE
              Exceptions:
                                                              3207.1 General. Shelf storage and storage in solid piles, solid
                1. Aisles crossing rack structures or storage piles,  piles on pallets and bin box storage in bin boxes not exceed-
                   that are used only for employee access, shall be  ing 5 feet (1524 mm) in any dimension, shall  be in accor-
                   not less than 24 inches (610 mm) wide.     dance with Section 3206 and this section.
                2. Aisles separating shelves classified as shelf stor-  3207.2 Fire protection. Where automatic sprinklers are
                   age shall be not  less than 30 inches (762 mm)  required by Table 3206.2, an approved automatic sprinkler
                   wide.                                      system shall be installed throughout the building or to 1-hour
              3206.10.1.1 Sprinklered buildings. Aisles  in sprin-  fire barriers constructed in accordance with Section 707 of
              klered buildings shall be not less than 44 inches (1118  the International Building Code. Openings in such fire barri-
              mm) wide. Aisles shall be not less than 96 inches (2438  ers shall be protected by opening protectives having a 1-hour
              mm) wide in high-piled storage areas exceeding 2,500  fire protection rating. The design and installation of the auto-
                             2
              square feet (232 m ) in area, that are accessible to the  matic sprinkler system and other  applicable fire protection
              public and designated to contain high-hazard commodi-  shall be in accordance with the International Building Code
              ties.                                           and NFPA 13.
                 Aisles shall be not less than 96 inches (2438 mm)  3207.2.1 Shelf storage. Shelf storage greater than 12 feet
              wide  in areas open to  the  public where mechanical  (3658 mm) but less than 15 feet (4572 mm) in height shall
              stocking methods are used.                         be in accordance with the fire protection requirements set
                                                                 forth in NFPA 13. Shelf storage 15 feet (4572 mm) or
                Exceptions:
                                                                 more in height shall be protected in an approved manner
                   1. Aisles in high-piled storage areas exceeding  with special fire protection, such as in-rack sprinklers.
                                           2
                     2,500 square  feet (232 m ) in area, that  are
                     open to the public and designated to contain  3207.3 Pile dimension and height limitations. Pile dimen-
                     high-hazard commodities,  and that  are  pro-  sions, the maximum permissible storage height and pile vol-
                                                              ume shall be in accordance with Table 3206.2.
                     tected by a sprinkler system designed for mul-
                     tiple-row  racks of high-hazard commodities,  3207.4 Arrays. Where an automatic sprinkler system design
                     shall be not less than 44 inches (1118 mm)  utilizes protection based on a closed array, array clearances
                     wide.                                    shall be provided and maintained as specified by the standard
                                                              used.