Page 360 - 2018_IFC
P. 360

FIRE SAFETY DURING CONSTRUCTION AND DEMOLITION



             the development, implementation and maintenance of a writ-             SECTION 3309
             ten plan establishing a fire prevention program at the project       FIRE REPORTING
             site  applicable throughout all  phases of the construction,  3309.1 Emergency telephone. Emergency telephone facili-
             repair, alteration or demolition work. The plan shall address  ties with ready access shall be provided in an approved loca-
             the requirements of this chapter and other applicable portions  tion at the construction site, or an approved equivalent means
             of this code, the duties of staff, and staff  training require-  of communication shall be provided. The street address of the
             ments. The plan shall be made available for review by the fire
                                                                  construction site and the emergency telephone number of the
             code official upon request.                          fire department shall be  posted adjacent to  the  telephone.
             3308.2 Program superintendent. The owner shall designate  Alternatively, where an equivalent means of communication
             a person  to be  the  fire prevention program  superintendent  has been approved, the site address and fire department emer-
             who shall be responsible for the fire prevention program and  gency telephone number shall be posted at the main entrance
             ensure that it is carried out through completion of the project.  to the site, in guard shacks and in the construction site office.
             The fire prevention program superintendent shall have the
             authority to enforce the provisions of this chapter and other
             provisions as necessary to secure the intent of this chapter.          SECTION 3310
             Where guard service is provided in accordance with NFPA         ACCESS FOR FIRE FIGHTING
             241, the superintendent shall be responsible for the guard ser-  3310.1 Required access. Approved vehicle access for fire fight-
             vice.                                                ing shall be provided  to  all construction or demolition  sites.
             3308.3 Prefire plans. The fire prevention program superin-  Vehicle access shall be provided to within 100 feet (30 480 mm)
             tendent shall develop and maintain an approved prefire plan  of temporary or permanent fire department connections. Vehi-
             in cooperation with the fire chief. The fire chief and the fire  cle access shall be provided by either temporary or permanent
             code official shall be notified of changes affecting the utiliza-  roads, capable of supporting vehicle loading under all weather
             tion of information contained in such prefire plans.  conditions. Vehicle access shall be maintained until permanent
                                                                  fire apparatus access roads are available.
             3308.4 Training. Training of responsible personnel in the
             use of fire protection equipment shall be the responsibility of  3310.2 Key boxes. Key boxes shall be provided as required
             the fire prevention program superintendent. Records of train-  by Chapter 5.
             ing shall be kept and made a part of the written plan for the
             fire prevention program.
                                                                                    SECTION 3311
             3308.5 Fire protection devices. The fire prevention program         MEANS OF EGRESS
             superintendent shall determine that all fire protection equip-
             ment is maintained and serviced in accordance with this code.  [BE] 3311.1 Stairways required. Where building construc-
             The quantity and type of fire protection equipment shall be  tion exceeds 40 feet (12 192 mm) in height above the lowest
             approved. Fire  protection  equipment  shall be inspected in  level of fire department vehicle access, a temporary or perma-
             accordance with the fire protection program.         nent stairway shall be provided. As construction progresses,
                                                                  such stairway shall be extended to within one floor  of the
             3308.6 Hot work  operations.  The  fire prevention program  highest point of construction having secured decking or floor-
             superintendent shall be responsible for supervising the permit  ing.
             system for hot work operations in accordance with Chapter 35.
                                                                  3311.2 Maintenance. Required means of egress and required
             3308.7 Impairment of fire protection systems. Impairments  accessible means of egress shall be maintained during con-
             to any fire protection system shall be in accordance with Sec-  struction and demolition, remodeling or alterations and addi-
             tion 901.                                            tions to any building.
               3308.7.1 Smoke detectors and smoke alarms. Smoke      Exception:  Approved temporary  means of egress  and
               detectors and smoke alarms located in an area where air-  accessible means of egress systems and facilities.
               borne construction  dust is  expected shall be  covered to
               prevent exposure to dust or shall be temporarily removed.
               Smoke detectors and alarms that were removed shall be                SECTION 3312
               replaced upon conclusion of dust-producing work. Smoke  WATER SUPPLY FOR FIRE PROTECTION
               detectors and smoke alarms that  were covered shall be  3312.1 When required. An approved water supply for fire
               inspected and cleaned, as necessary, upon conclusion of  protection, either temporary or permanent, shall be made
               dust-producing work.
                                                                  available as soon as combustible material arrives on the site.
             3308.8  Temporary covering of fire  protection  devices.
             Coverings placed on or over fire protection devices to protect
             them from damage  during  construction processes shall be              SECTION 3313
             immediately removed upon the completion of the construc-               STANDPIPES
             tion processes in the room or area in which the devices are  3313.1 Where required. In buildings required to have stand-
             installed.                                           pipes by Section 905.3.1, not less than one standpipe shall be





             2018 INTERNATIONAL FIRE CODE ®                                                                      327
  Copyrighted © 2017 by, or licensed to, ICC (ALL RIGHTS RESERVED); licensed to UL, LLC pursuant to License Agreement with ICC. No further reproductions authorized or distribution authorized.
  ANY UNAUTHROIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT; AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
   355   356   357   358   359   360   361   362   363   364   365