Page 41 - 2018_IFC
P. 41
SCOPE AND ADMINISTRATION
105.6.11 Cutting and welding. An operational permit is 4. To store, handle or use Class IIIB liquids in tanks
required to conduct cutting or welding operations within or portable tanks for fueling motor vehicles at
the jurisdiction. motor fuel-dispensing facilities or where con-
nected to fuel-burning equipment.
105.6.12 Dry cleaning. An operational permit is required
to engage in the business of dry cleaning or to change to a Exception: Fuel oil and used motor oil used for
more hazardous cleaning solvent used in existing dry space heating or water heating.
cleaning equipment. 5. To remove Class I or II liquids from an under-
ground storage tank used for fueling motor vehi-
105.6.13 Exhibits and trade shows. An operational per-
mit is required to operate exhibits and trade shows. cles by any means other than the approved,
stationary on-site pumps normally used for dis-
105.6.14 Explosives. An operational permit is required for pensing purposes.
the manufacture, storage, handling, sale or use of any 6. To operate tank vehicles, equipment, tanks, plants,
quantity of explosives, explosive materials, fireworks or terminals, wells, fuel-dispensing stations, refiner-
pyrotechnic special effects within the scope of Chapter 56.
ies, distilleries and similar facilities where flam-
Exception: Storage in Group R-3 occupancies of mable and combustible liquids are produced,
smokeless propellant, black powder and small arms processed, transported, stored, dispensed or used.
primers for personal use, not for resale and in accor- 7. To place temporarily out of service (for more than
dance with Section 5606.
90 days) an underground, protected above-ground
105.6.15 Fire hydrants and valves. An operational per- or above-ground flammable or combustible liquid
mit is required to use or operate fire hydrants or valves tank.
intended for fire suppression purposes that are installed on 8. To change the type of contents stored in a flamma-
water systems and provided with ready access from a fire ble or combustible liquid tank to a material that
apparatus access road that is open to or generally used by poses a greater hazard than that for which the tank
the public. was designed and constructed.
Exception: A permit is not required for authorized 9. To manufacture, process, blend or refine flamma-
employees of the water company that supplies the sys- ble or combustible liquids.
tem or the fire department to use or operate fire 10. To engage in the dispensing of liquid fuels into the
hydrants or valves.
fuel tanks of motor vehicles at commercial, indus-
105.6.16 Flammable and combustible liquids. An opera- trial, governmental or manufacturing establish-
tional permit is required: ments in accordance with Section 5706.5.4 or to
engage in on-demand mobile fueling operations in
1. To use or operate a pipeline for the transportation accordance with Section 5707.
within facilities of flammable or combustible liq-
uids. This requirement shall not apply to the off- 11. To utilize a site for the dispensing of liquid fuels
site transportation in pipelines regulated by the from tank vehicles into the fuel tanks of motor
Department of Transportation (DOTn) nor does it vehicles, marine craft and other special equipment
apply to piping systems. at commercial, industrial, governmental or manu-
facturing establishments in accordance with Sec-
2. To store, handle or use Class I liquids in excess of tion 5706.5.4 or, where required by the fire code
5 gallons (19 L) in a building or in excess of 10 official, to utilize a site for on-demand mobile
gallons (37.9 L) outside of a building, except that a fueling operations in accordance with Section
permit is not required for the following: 5707.
2.1. The storage or use of Class I liquids in the 105.6.17 Floor finishing. An operational permit is
fuel tank of a motor vehicle, aircraft, required for floor finishing or surfacing operations exceed-
2
motorboat, mobile power plant or mobile ing 350 square feet (33 m ) using Class I or Class II liq-
heating plant, unless such storage, in the uids.
opinion of the fire code official, would 105.6.18 Fruit and crop ripening. An operational permit
cause an unsafe condition.
is required to operate a fruit- or crop-ripening facility or
2.2. The storage or use of paints, oils, varnishes conduct a fruit-ripening process using ethylene gas.
or similar flammable mixtures where such 105.6.19 Fumigation and insecticidal fogging. An opera-
liquids are stored for maintenance, painting tional permit is required to operate a business of fumiga-
or similar purposes for a period of not more tion or insecticidal fogging, and to maintain a room, vault
than 30 days. or chamber in which a toxic or flammable fumigant is
3. To store, handle or use Class II or Class IIIA liq- used.
uids in excess of 25 gallons (95 L) in a building or 105.6.20 Hazardous materials. An operational permit is
in excess of 60 gallons (227 L) outside a building, required to store, transport on site, dispense, use or handle
except for fuel oil used in connection with oil- hazardous materials in excess of the amounts listed in
burning equipment. Table 105.6.20.
8 2018 INTERNATIONAL FIRE CODE ®
Copyrighted © 2017 by, or licensed to, ICC (ALL RIGHTS RESERVED); licensed to UL, LLC pursuant to License Agreement with ICC. No further reproductions authorized or distribution authorized.
ANY UNAUTHROIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT; AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.