APPENDIX J

                                        BUILDING INFORMATION SIGN



                            The provisions contained in this appendix are not mandatory unless specifically referenced in
                                          the adopting ordinance or legislation of the jurisdiction.


             User note:
                About this appendix: Appendix J provides design, installation and maintenance requirements for a Building Information Sign (BIS), a fire
                service tool to be utilized in the crucial, initial response of fire fighters to a structure fire. The BIS placard is designed to be utilized within
                the initial response time frame of an incident to assist fire fighters in their tactical sizing up of a situation as soon as possible after arrival on
                the scene of a fire emergency. The BIS design is in the shape of a fire service Maltese Cross and includes five spaces (the four wings plus
                the centerpiece of the cross symbol) in which information is placed about the tactical considerations of construction type and hourly rating,
                fire protection systems, occupancy type, content hazards and special features that could affect tactical decisions and operations.


                               SECTION J101                              height of 42 inches (1067 mm) above the walking
                                 GENERAL                                 surface on the address side of the building or struc-
             J101.1 Scope. New buildings shall have a building informa-  ture.
             tion sign(s) that shall comply with Sections J101.1.1 through  3. Conspicuously placed inside  an  enclosed entrance
             J101.7. Existing buildings shall be brought into conformance  lobby, on any vertical surface within 10 feet (254
             with Sections J101.1 through J101.9 when one of the follow-  mm) of the entrance door at a minimum height of 42
             ing occurs:                                                 inches (1067 mm) above the walking surface.
               1. The  fire department conducts  an annual  inspection  4. Inside the building’s fire command center.
                  intended to verify compliance with this section, or any  5. On the exterior of the fire alarm control unit or on
                  required inspection.                                   the wall immediately adjacent to the fire alarm con-
               2. A change in use or occupancy has occurred.             trol unit door where the alarm panel is located in the
               Exceptions:                                               enclosed main lobby.
                  1. Group U occupancies.                            J101.1.2 Sign features.  The building information  sign
                                                                     shall consist of all of the following:
                  2.  One- and two-family dwellings.
                                                                       1. White reflective background with red letters.
               J101.1.1  Sign location.  The  building information sign
               shall be placed at one of the following locations:      2. Durable material.
                  1. On the entry door or sidelight at a minimum height  3. Numerals shall be  Roman or Latin numerals, as
                    of 42 inches (1067 mm) above the walking surface     required, or alphabet letters.
                    on the address side of the building or structure.  4. Permanently affixed to the building or structure in
                                                                         an approved manner.
                  2. On the exterior surface of the building or structure
                    on either side of the entry door, not more than 3 feet  J101.1.3 Sign shape. The building information sign shall
                    (76  mm)  from the  entrance door, at a minimum  be a Maltese cross as shown in Figure J101.1.3.

                                                            (Top)

                                                           IIA & IIIA





                                     (Left)   MH             TC              PS     (Right)





                                                           E, A & M


                                                           (Bottom)
                                                          FIGURE J101.1.3
                                         EXAMPLE OF COMPLETED BUILDING INFORMATION SIGN