APPENDIX K



           K102.2.5 Joints. Joints made in or between smoke barri-  level  of exit discharge, including  the  level  of exit dis-
           ers shall comply with the International Building Code.  charge.
              Exception:  Approved existing materials and methods  K102.4 Automatic fire alarm system. Fire areas containing
              of construction.                                ambulatory care facilities shall be provided with an electroni-
           K102.2.6 Duct and air transfer openings. Penetrations  cally supervised automatic smoke detection system installed
           in a smoke barrier by duct and air-transfer openings shall  within the ambulatory care facility and in public use areas
           comply with  Section 717 of the  International Building  outside of tenant spaces, including public corridors and ele-
           Code.                                              vator lobbies.
              Exception: Where existing duct and air-transfer open-  Exception: Buildings equipped throughout with an auto-
              ings in smoke barriers exist without  smoke dampers,  matic sprinkler system  in accordance with  Section
              they shall be permitted to remain. Any changes to exist-  903.3.1.1, provided that the  occupant notification appli-
              ing smoke dampers shall be submitted for review and  ances will activate throughout the notification zones upon
              approved in accordance with Section 717 of the Inter-  sprinkler waterflow.
              national Building Code.                         K102.5 Waste and linen chutes. In ambulatory care facili-
           K102.2.7 Independent egress. A means of egress shall be  ties, existing waste and linen chutes shall comply with Sec-
           provided from each smoke compartment created by smoke  tions K102.5.1 through K102.5.5.
           barriers without having to return through the smoke com-  K102.5.1 Enclosures. Chutes shall be enclosed with 1-
           partment from which means of egress originated.       hour fire-resistance-rated construction. Opening protec-
         K102.3 Automatic  sprinkler system. An automatic sprin-  tives shall be in accordance with Section 716 of the Inter-
         kler system shall  be provided in ambulatory care facilities  national Building Code and have a fire protection rating
         where required by Sections K102.3.1 and K102.3.2.       of not less than1 hour.
           K102.3.1 Types IIB, IIIB and VB construction. An      K102.5.2 Chute intakes. Chute intakes shall comply with
           automatic sprinkler system shall be provided throughout  Section K102.5.2.1 or K102.5.2.2.
           the entire floor containing an ambulatory care facility in  K102.5.2.1 Chute intake direct  from corridor.
           Type IIB, IIIB and VB construction where either of the  Where intake to chutes is direct from a  corridor, the
           following conditions exist at any time:
                                                                   intake opening  shall be equipped with a chute-intake
              1. Four or more care recipients are rendered incapable  door in accordance with  Section 716 of the  Interna-
                of self-preservation.                              tional Building Code and have a fire protection rating
              2. One or more care recipients that are rendered inca-  of not less than 1 hour.
                pable of self-preservation are located at other than  K102.5.2.2  Chute  intake via a chute-intake  room.
                the level of exit discharge serving such a facility.  Where the intake to chutes is accessed through a chute-
              In buildings where ambulatory care is provided on lev-  intake room, the room shall be enclosed  with 1-hour
           els other than the  level of exit discharge, an  automatic  fire-resistance-rated construction. Opening protectives
           sprinkler system shall be installed throughout the entire  for the intake room shall be in accordance with Section
           floor where such care is provided, all floors below and all  716 of the International Building Code and have a fire
                                                                                              3
           floors between the level of ambulatory care and the nearest  protection rating of not less than  /  hour. Opening pro-
                                                                                               4
           level  of exit discharge, including the  level of exit  dis-  tectives for the chute enclosure shall be in accordance
           charge.                                                 with Section K102.5.1.
           K102.3.2 High-rise buildings. In high-rise buildings con-  K102.5.3 Automatic sprinkler system. Chutes shall be
           taining ambulatory care facilities, an automatic sprinkler  equipped with an approved automatic sprinkler system in
           system shall be provided throughout the entire floor con-  accordance with Section 903.2.11.2.
           taining an ambulatory care facility where either of the fol-  K102.5.4 Chute discharge rooms. Chutes shall terminate
           lowing conditions exist at any time:
                                                                 in a dedicated chute discharge room. Such rooms shall be
              1. Four or more care recipients are rendered incapable  separated from the remainder of the building by not less
                of self-preservation.                            than  1-hour fire-resistance-rated construction.  Opening
              2. One or more care recipients that are rendered inca-  protectives shall be in accordance with Section 716 of the
                pable of self-preservation are located at other than  International Building Code and have a fire protection rat-
                the level of exit discharge serving such a facility.   ing of not less than 1 hour.
              In buildings where ambulatory care is provided on lev-  K102.5.5 Chute discharge protection. Chute discharges
           els other than the  level of  exit discharge, an automatic  shall be equipped with a self-closing or automatic-closing
           sprinkler system shall be installed throughout the entire  opening protective in accordance with Section 716 of the
           floor where such care is provided, all floors below and all  International Building Code and have a fire protection rat-
           floors between the level of ambulatory care and the nearest  ing of not less than 1 hour.







         556                                                                        2018 INTERNATIONAL FIRE CODE ®