Page 71 - 2018_IFC
P. 71

DEFINITIONS



                Division 1.3                                       Combustible fibers,  other than densely packed baled
                Division 1.4                                         cotton,  where manufactured, generated or used  in
                Division 1.5                                         such a manner that the concentration and conditions
                Division 1.6                                         create  a fire  or explosion  hazard based on
                                                                     information prepared in accordance with  Section
              Organic peroxides, unclassified detonable              414.1.3 of the International Building Code
              Oxidizers, Class 4                                   Consumer fireworks, 1.4G (Class C, Common)
              Unstable (reactive) materials, Class 3  detonable, and  Cryogenic fluids, oxidizing
                Class 4
                                                                   Flammable solids
           Occupancies containing explosives not classified as H-  Organic peroxides, Class II and III
           1.  The following occupancies containing explosive mate-  Oxidizers, Class 2
           rials shall be classified as follows:                   Oxidizers, Class 3, that are used or stored in normally
              1. Division  1.3 explosive materials that are used and  closed  containers or systems pressurized at 15
                maintained in a form where either confinement or     pounds per square inch gauge (103 kPa) or less
                configuration will  not elevate the hazard from  a  Oxidizing gases
                mass fire hazard to mass explosion hazard shall be  Unstable (reactive) materials, Class 2
                allowed in Group H-2 occupancies.                  Water-reactive materials, Class 2
                                                                 High-hazard Group H-4. Buildings and structures con-
              2. Articles,  including articles packaged for  shipment,
                that are not  regulated as  a  Division 1.4  explosive  taining materials that are health hazards shall be classified
                under Bureau of Alcohol,  Tobacco,  Firearms  and  as Group H-4. Such materials shall include, but not be lim-
                Explosives regulations, or unpackaged articles used  ited to, the following:
                in process operations that do not propagate a detona-  Corrosives
                tion  or deflagration between  articles shall be   Highly toxic materials
                allowed in H-3 occupancies.                        Toxic materials
           High-hazard Group H-2. Buildings and structures con-  High-hazard Group H-5. Semiconductor fabrication
           taining materials that pose a deflagration hazard or a haz-  facilities and comparable research and development areas
           ard from accelerated burning shall be classified as Group  in which hazardous production materials (HPM) are used
           H-2. Such materials shall include, but not be limited to, the  and the aggregate  quantity of  materials is in excess of
           following:                                            those listed in Tables 5003.1.1(1) and 5003.1.1(2) shall be
                                                                 classified as Group H-5. Such facilities and areas shall be
              Class I, II  or IIIA flammable or  combustible liquids  designed and constructed in  accordance with Section
                that are used or stored in normally open containers  415.11 of the International Building Code.
                or systems, or  in closed  containers  or systems  [BG] Institutional Group I. Institutional Group I occu-
                pressurized at more than 15 pounds per square inch  pancy includes, among others,  the  use of  a building  or
                gauge (103.4 kPa)                                structure, or a portion thereof, in which care or supervision
              Combustible dusts  where manufactured, generated  or  is provided to persons who are or are not capable of self-
                used in  such a manner that the concentration and  preservation without physical assistance or in which per-
                conditions create a fire or explosion hazard based on  sons are detained for penal or correctional purposes or in
                information prepared in  accordance with Section  which the  liberty of the occupants is restricted. Institu-
                414.1.3 of the International Building Code       tional occupancies shall be classified as Group I-1, I-2, I-3
              Cryogenic fluids, flammable                        or I-4.
              Flammable gases
              Organic peroxides, Class I                           [BG] Institutional Group I-1. Institutional Group I-1
                                                                   occupancy shall include buildings, structures or por-
              Oxidizers, Class 3, that are used or stored in normally  tions thereof for more than 16 persons, excluding staff,
                open containers or systems, or in closed containers or  who reside on a 24-hour basis in a supervised environ-
                systems pressurized at  more than 15 pounds per    ment and receive custodial care. Buildings of Group I-1
                square inch gauge (103.4 kPa)
                                                                   shall be classified as one of the occupancy conditions
              Pyrophoric liquids, solids and gases, nondetonable   indicated below. This group shall include, but not be
                Unstable (reactive) materials, Class 3, nondetonable  limited to, the following:
                Water-reactive materials, Class 3
                                                                     Alcohol and drug centers
           High-hazard Group H-3. Buildings and structures con-      Assisted living facilities
           taining materials that readily support combustion or that  Congregate care facilities
           pose a physical hazard shall be classified as Group H-3.  Group homes
           Such materials shall include, but not be limited to, the fol-  Halfway houses
           lowing:                                                   Residential board and care facilities
              Class I, II  or IIIA flammable or  combustible liquids  Residential board and custodial care facilities
                that are used or stored in normally closed containers  Social rehabilitation facilities
                or systems pressurized at 15 pounds per square inch  [BG] Condition 1. This occupancy condition shall
                gauge (103.4 kPa) or less.                           include buildings in which all persons receiving cus-



         38                                                                         2018 INTERNATIONAL FIRE CODE ®
  Copyrighted © 2017 by, or licensed to, ICC (ALL RIGHTS RESERVED); licensed to UL, LLC pursuant to License Agreement with ICC. No further reproductions authorized or distribution authorized.
  ANY UNAUTHROIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT; AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
   66   67   68   69   70   71   72   73   74   75   76