Page 556 - 2018_Complete_14_Collection (1)_Neat
P. 556
WOOD
ROOF SHEATHING
EDGE NAILING PER
TABLE 2304.10.1 (TYP)
4′-0″ MAX 2x BLOCKING ATTACHED TO 2x BLOCKING
TRUSS TOP CHORD PER
TABLE 2304.10.1,
ITEM 1
MIDDLE 1/3 AVAILABLE PRE-ENGINEERED TRUSSES
FOR VENT HOLES. (CONT.
VENT NOT ALLOWED)
NAILING PER TABLE 2304.10.1, ITEM 1
BRACING a
BRACED WALL LINE PROVIDE VENTING PER
SECTION 1202.2
6′-0″ MAX
a. Methods of bracing shall be as described in Table 2308.6.3(1) DWB, WSP, SFB, GB, PBS, PCP or HPS.
For SI: 1 foot = 304.8 mm.
FIGURE 2308.6.7.2(1)
BRACED WALL LINE TOP PLATE CONNECTION
PROVIDE VENTING
PER SECTION 1202.2 EDGE NAILING PER
B (NOT SHOWN) TABLE 2304.10.1 (TYP)
EDGE NAILING PER
TABLE 2304.10.1 (TYP) ROOF SHEATHING
ATTACH BLOCKING TO a
TRUSS TOP CHORD BRACING
PER TABLE 2304.10.1 A
ITEM 1
4′-0″ MAX 2x BLOCKING (4) 2x FILLER BLOCKS
SIDES & WEB FILLER.
ATTACH PER TABLE
BETWEEN TRUSS
2304.10.1, ITEM 1
WEBS
2x FLAT
BLOCKING
BRACING a WALL BRACING
PRE-ENGINEERED
BRACED WALL TRUSSES BELOW NOT SHOWN
LINE
NAILING IN
ACCORDANCE
WITH TABLE 2304.10.1,
6′-0″ MAX ITEM 1
SECTION ELEVATION
A B
a. Methods of bracing shall be as described in Table 2308.6.3(1) DWB, WSP, SFB, GB, PBS, PCP or HPS.
For SI: 1 foot = 304.8 mm.
FIGURE 2308.6.7.2(2)
BRACED WALL PANEL TOP PLATE CONNECTION
2018 INTERNATIONAL BUILDING CODE ® 529