Page 559 - 2018_Complete_14_Collection (1)_Neat
P. 559

WOOD



                                                             WHERE FOOTING SECTION “A” IS MORE THAN 8′-0″
                                                             PROVIDE METAL TIE 16GA x 1½″ x 4′-0″ MIN., EACH SIDE
                                               2′-0″ MIN.    W/8-16d COMMON NAILS
                                SILL PLATE                   EACH SIDE OF SPLICE
                                              SPLICE                              2-2x PLATE


                            CONCRETE
                            STEPPED FOOTING                                        2x CRIPPLED
                                                                                   STUD WALL





                                      FOOTING SECTION “A”

                                                    NOTE: WHERE FOOTING SECTION “A”
                                                    IS LESS THAN 8′-0″ LONG IN A
                                                    25′-0″ TOTAL LENGTH WALL, PROVIDE
                                                    BRACING AT CRIPPLE STUD WALL
         For SI: 1 inch = 25.4 mm, 1 foot = 304.8 mm.
                                                     FIGURE 2308.6.8.3
                                           STEPPED FOOTING CONNECTION DETAILS

                           shall  be  provided  at  the  ends  of  each  rafters and ceiling joists such as ridge board, hips and valleys
                           braced wall panel for the first story to  shall be designed as beams.
                           the foundation connection. In all cases,  2308.7.1 Ceiling joist spans. Spans for ceiling joists shall
                           the hold-down connector force shall be  be in accordance with Table 2308.7.1(1) or 2308.7.1(2).
                           transferred to the foundation.        For other grades and species, and other loading conditions,
                       3.4. Cripple walls shall not be permitted.  refer to the AWC STJR.
              2308.6.10.2  Limitations of concrete or masonry in  2308.7.2 Rafter spans. Spans for rafters shall be in accor-
              Seismic Design Categories  D and E.  In  Seismic   dance  with  Table  2308.7.2(1),  2308.7.2(2),  2308.7.2(3),
              Design Categories D and E, concrete or masonry walls  2308.7.2(4), 2308.7.2(5) or 2308.7.2(6). For other grades
              and stone or masonry veneer shall not extend above a  and  species  and  other  loading  conditions,  refer  to  the
              basement.                                          AWC  STJR.  The  span  of  each  rafter  shall  be  measured
                                                                 along the horizontal projection of the rafter.
                Exception: In structures assigned to Seismic Design
                Category D, stone and masonry veneer is permitted  2308.7.3 Ceiling joist and rafter framing. Rafters shall
                to be used in the first story above grade plane, pro-  be framed directly opposite each other at the ridge. There
                vided that the following criteria are met:       shall be a ridge board not less than 1-inch (25 mm) nomi-
                   1. Type  of  brace  in  accordance  with  Section  nal thickness at ridges and not less in depth than the cut
                     2308.6.1 shall be WSP and the allowable shear  end of the rafter. At valleys and hips, there shall be a sin-
                     capacity  in  accordance  with  Section  2306.3  gle valley or hip rafter not less than 2-inch (51 mm) nomi-
                     shall be not less than 350 plf (5108 N/m).  nal thickness and not less in depth than the cut end of the
                   2. The braced wall panels in the first story shall  rafter.
                     be located at each end of the braced wall line  2308.7.3.1 Ceiling joist and rafter connections. Ceil-
                     and not more than 25 feet (7620 mm) on cen-   ing joists and rafters shall be nailed to each other and
                     ter, and the total length of braced wall panels  the  assembly  shall  be  nailed  to  the  top  wall  plate  in
                     shall be not less than 45 percent of the braced  accordance with Tables 2304.10.1 and 2308.7.5. Ceil-
                     wall line length.                             ing joists shall be continuous or securely joined where
                   3. Hold-down connectors shall be provided at the  they  meet  over  interior  partitions  and  be  fastened  to
                                                                   adjacent  rafters  in  accordance  with  Tables  2304.10.1
                     ends of braced walls for the first floor to foun-  and 2308.7.3.1 to provide a continuous rafter tie across
                     dation  with  an  allowable  capacity  of  2,100  the building where such joists are parallel to the rafters.
                     pounds (9341 N).                              Ceiling joists shall have a bearing surface of not less
                   4. Cripple walls shall not be permitted.        than 1 /  inches (38 mm) on the top plate at each end.
                                                                        1
                                                                         2
         2308.7 Roof  and ceiling  framing.  The  framing  details    Where  ceiling  joists  are  not  parallel  to  rafters,  an
         required in this section apply to roofs having a slope of not  equivalent  rafter  tie  shall  be  installed  in  a  manner  to
         less than three units vertical in 12 units horizontal (25-percent  provide a continuous tie across the building, at a spac-
         slope). Where the roof slope is less than three units vertical in  ing of not more than 4 feet (1219 mm) on center. The
         12 units horizontal (25-percent slope), members supporting  connections  shall  be  in  accordance  with  Tables
                                                                   2308.7.3.1 and 2304.10.1, or connections of equivalent


         532                                                                    2018 INTERNATIONAL BUILDING CODE  ®
  Copyrighted © 2017 by, or licensed to, ICC (ALL RIGHTS RESERVED); licensed to UL, LLC pursuant to License Agreement with ICC. No further reproductions authorized or distribution authorized.
  ANY UNAUTHROIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT; AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
   554   555   556   557   558   559   560   561   562   563   564