Page 109 - ICC IEBC 2018
P. 109

APPENDIX A



         [BS] A111.6 Shear walls (In-plane loading).                            SECTION A112
           [BS] A111.6.1 Wall story force. The wall story force dis-       ANALYSIS AND DESIGN
           tributed to a shear wall at any diaphragm level shall be the  [BS] A112.1 General. The following requirements are appli-
           lesser value calculated as:                        cable to both the general procedure and the special procedure
                                                              for analyzing vertical elements of the lateral force-resisting
            F wx  =  0.8S D1 (  W wx  + W /2)  d  (Equation A1-13)  system.
           but need not exceed                                [BS]  A112.2  In-plane shear of unreinforced masonry
                                                              walls.
            F wx  =  0.8S D1 W wx  +  v D  (Equation A1-14)
                              u
                                                                 [BS] A112.2.1 Flexural rigidity. Flexural components of
           [BS]  A111.6.2 Wall story shear. The wall story  shear  deflection need not be considered in determining the rigid-
           shall be the sum of the wall story forces at and above the  ity of an unreinforced masonry wall.
           level of consideration.                               [BS] A112.2.2 Shear walls with openings. Wall  piers
            V wx  =  ΣF wx                 (Equation A1-15)      shall  be analyzed according  to the following procedure,
                                                                 which is diagrammed in Figure A112.2.2.
           [BS] A111.6.3 Shear wall analysis. Shear walls shall    1. For any pier,
           comply with Section A112.
                                                                        1.1. The pier shear capacity  shall  be calculated
           [BS] A111.6.4  New seismic  force-resisting  elements.           as:
           New seismic force-resisting elements such as moment
           frames, braced frames or shear walls shall be designed as        v  = v A n          (Equation A1-18)
                                                                            a
                                                                                m
           required by  the  building code, except that the seismic         where:
           forces shall be as specified in Section A111.6.1, and the        A  =  area of net mortared or grouted section
           story drift ratio shall be limited to 0.015, except as further    n  of a wall or wall pier.
           limited by Section A112.4.2 for moment frames.
                                                                        1.2. The pier rocking shear capacity shall be cal-
         [BS] A111.7 Out-of-plane forces—unreinforced masonry               culated as:
         walls.
                                                                            V  = 0.9P D/H       (Equation A1-19)
           [BS] A111.7.1 Allowable  unreinforced masonry wall                r     D
           height-to-thickness ratios. The  provisions of Section  2. The wall piers at any level are acceptable if they
           A110.2  are  applicable, except the allowable height-to-  comply with one of the following modes of behav-
           thickness ratios given in Table A110.2 shall be determined  ior:
           from Figure A111.4.1 as follows:
                                                                        2.1. Rocking controlled  mode. Where  the pier
              1. In Region 1, height-to-thickness ratios for buildings      rocking shear capacity is less than the pier
                with crosswalls may be used if qualifying crosswalls        shear capacity, in other words, V  < v , for
                                                                                                           a
                                                                                                       r
                are present in all stories.                                 each pier in a level, forces in the wall at that
              2. In Region 2, height-to-thickness ratios for buildings      level, V , shall be distributed to each pier in
                                                                                  wx
                with crosswalls may be used whether or not qualify-         proportion to P D/H.
                                                                                        D
                ing crosswalls are present.                                 For the wall at that level:
              3. In Region 3, height-to-thickness ratios for “all other     0.7V  < ΣV          (Equation A1-20)
                buildings” shall be used whether or not qualifying             wx    r
                crosswalls are present.                                 2.2. Shear controlled mode. Where the pier shear
                                                                            capacity is less than the pier rocking capac-
           [BS]  A111.7.2 Walls with diaphragms in  different               ity, in other words, v  < V  in one or more
           regions. Where diaphragms above  and  below  the wall            pier(s) in a level, forces in the wall at the
                                                                                                  r
                                                                                             a
           under consideration have demand-capacity ratios in differ-       level, V , shall be distributed to each pier in
           ent regions of Figure A11.4.1, the lesser height-to-thick-       proportion to D/H.
                                                                                  wx
           ness ratio shall be used.
                                                                            For each pier at that level:
         [BS] A111.8 Open-front design procedure. A single-story
         building with an open front on one side and crosswalls parallel    V  < v a            (Equation A1-21)
                                                                             p
         to the open front may be designed by the following procedure:
                                                                            and
           1. Effective diaphragm  span,  L , for  use in Figure
                                        i                                   V  < V              (Equation A1-22)
              A111.4.1  shall be determined in accordance with  the          p   r
              following formula:                                              If V  < v  for each pier and V  > V  for one
                                                                                                     p
                                                                                                         r
                                                                                    a
                                                                                 p
                                                                            or more  piers, such  piers shall be  omitted
              L  = 2[(W /W )L + L]         (Equation A1-16)
                        d
                     w
               i
                                                                            from the analysis, and the procedure shall be
           2. Diaphragm demand-capacity ratio shall be calculated           repeated for the remaining piers, unless the
              as:                                                           wall is strengthened and reanalyzed.
              DCR = 2.1S (W  + W )/[(v D) + V ]                    3. Masonry pier tension stress. Unreinforced masonry
                           d
                                w
                                    u
                       D1
                                          cb
                                           (Equation A1-17)          wall piers need not be analyzed for tension stress.
         90                                                             2018 INTERNATIONAL EXISTING BUILDING CODE  ®
  Copyrighted © 2017 by, or licensed to, ICC (ALL RIGHTS RESERVED); licensed to UL, LLC pursuant to License Agreement with ICC. No further reproductions authorized or distribution authorized.
  ANY UNAUTHROIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT; AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
   104   105   106   107   108   109   110   111   112   113   114