Page 106 - ICC IEBC 2018
P. 106

APPENDIX A



                  in the definition of classes of masonry is permitted to  be subject  to  special inspection, prior to placement of the
                  avoid unnecessary testing.                      anchor and grout or adhesive in the drilled hole. Five percent
                  [BS] A106.2.3.9  Pointing. Deteriorated mortar joints  of all anchors resisting tension forces shall be subject to a
                  in  unreinforced  masonry walls shall be pointed  in  direct-tension test, and an additional 20 percent shall be
                  accordance with the following requirements:     tested using a calibrated torque wrench. Testing shall be per-
                                                                  formed in accordance with Section A107.5.
                    1. Joint preparation.  Deteriorated mortar shall  be
                       cut out by means of a toothing chisel or nonimpact  Exception: New bolts that extend through the wall with
                       power tool  until sound mortar  is reached, to  a  steel plates on the far side of the wall need not be tested.
                                      3
                       depth not less than  /  inch (19.1 mm) or twice the  [BS] A107.5 Tests of anchors in unreinforced masonry
                                       4
                       thickness of the joint,  whichever is less, but not  walls. Tests of anchors in unreinforced masonry walls shall be
                       greater than 2 inches (50 mm). Care shall be taken  in accordance with  Sections A107.5.1 through A107.5.3.
                       not to damage the masonry edges. After cutting is  Results of all tests shall be reported to the authority having
                       complete, all loose material shall be removed with  jurisdiction. The report shall include the test results of maxi-
                       a brush, or air or water stream.           mum load for each test; pass-fail results; corresponding anchor
                                                                  size and type; orientation  of  loading; details  of the  anchor
                    2. Mortar preparation. The mortar mix  shall be
                       proportioned as required by the construction  installation, testing apparatus and embedment; wall thickness;
                       specifications and manufacturer’s approved  and joist orientation and proximity to the tested anchor.
                       instructions.                                 [BS] A107.5.1 Direct tension testing of existing anchors
                                                                     and new anchors. The test apparatus shall be supported by
                    3. Packing. The joint into which the mortar is to be
                       packed shall be dampened but without free-stand-  the masonry wall. The test procedure for prequalification
                       ing water. The mortar shall be tightly packed into  of tension  and shear anchors shall  comply  with  ASTM
                                                 1
                       the joint in layers not exceeding  /  inch (6.4 mm)  E488. Existing wall anchors shall be given a preload of 300
                                                  4                  pounds (1335 N) before establishing a datum for recording
                       deep until it is filled; then it shall be tooled to a
                       smooth surface to match the original profile.  elongation. The tension test load reported shall be recorded
                                                                       1
                                                                     at  /  inch (3.2 mm) relative movement between the exist-
                                                                        8
                    Nothing shall prevent pointing of any masonry wall  ing anchor and the adjacent masonry surface. New embed-
                  joints before testing is performed in accordance  with  ded tension anchors shall be subject to a direct tension load
                  Section A106.2.3, except as required in Section A107.2.  of not less than 2.5 times the design load but not less than
                                                                     1,500 pounds (6672 N) for five minutes.
                                                                       Exception: Where  obstructions occur, the distance
                              SECTION A107
                            QUALITY CONTROL                            between the anchor and the test apparatus support shall
                                                                       be not less than one-half the wall thickness for existing
             [BS] A107.1 Pointing. Preparation and mortar pointing shall  anchors and 75 percent of the embedment  length  for
             be performed with special inspection.                     new embedded anchors.
               Exception: At the discretion of the code official, inciden-  [BS] A107.5.2 Torque testing of new anchors. Anchors
               tal pointing may be performed without special inspection.  embedded in unreinforced masonry walls shall be tested
             [BS] A107.2 Masonry shear tests. In-place masonry shear  using a  torque-calibrated  wrench to the  following mini-
             tests shall comply with Section A106.2.3.1.  Testing of  mum torques:
             masonry for determination of tensile-splitting strength shall  1 / -inch-diameter  (12.7 mm)  bolts: 40 foot pounds
                                                                        2
             comply with Section A106.2.3.2.                           (54.2 N-m).
             [BS] A107.3 Existing wall anchors. Existing wall anchors  5 / -inch-diameter  (15.9 mm)  bolts: 50 foot pounds
                                                                        8
             used as all or part of the required tension anchors shall be  (67.8 N-m).
             tested in pullout  according to Section A107.5.1. Not fewer  3 / -inch-diameter  (19.1 mm)  bolts: 60 foot pounds
                                                                        4
             than four anchors tested per floor shall be tested in pullout,  (81.3 N-m).
             with not fewer than two tests at walls with joists framing into
             the wall and two tests at walls with joists parallel to the wall,  [BS] A107.5.3 Prequalification test for bolts and other
             but not less than 10 percent of the total number of existing  types of anchors. ASTM  E488 or  the test procedure  in
             tension anchors at each level.                          Section A107.5.1 is permitted to be used to determine ten-
                                                                     sion or shear strength values for anchors greater than those
             [BS] A107.4 New wall anchors. New wall anchors embed-   permitted by Table A108.1(2). Anchors shall be installed
             ded in URM walls shall be subject to special inspection prior  in the same manner and using the same materials as will
             to  placement of  the  anchor and grout or adhesive in the  be used in  the actual construction. Not fewer than five
             drilled hole. Five percent of all anchors that do not extend  tests for  each bolt size and type shall be performed for
             through the wall shall be subject to a direct-tension test, and  each class of masonry in which they are proposed to be
             an additional 20 percent shall be tested  using a calibrated  used. The tension  and shear strength  values for  such
             torque wrench. Testing shall be performed in accordance with  anchors  shall be the  lesser  of the average  ultimate load
             Section A107.5.                                                                              1
                                                                     divided by 5.0 or the average load at which  /  inch (3.2
                                                                                                           8
               New wall anchors embedded in URM walls resisting ten-  mm) elongation occurs for each size and type of anchor
             sion forces or a combination of tension and shear forces shall  and class of masonry.

             2018 INTERNATIONAL EXISTING BUILDING CODE ®                                                          87
  Copyrighted © 2017 by, or licensed to, ICC (ALL RIGHTS RESERVED); licensed to UL, LLC pursuant to License Agreement with ICC. No further reproductions authorized or distribution authorized.
  ANY UNAUTHROIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT; AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
   101   102   103   104   105   106   107   108   109   110   111