Page 96 - ICC IEBC 2018
P. 96

CONSTRUCTION SAFEGUARDS



             comply  with the provisions of the applicable governing  Code, not less than one standpipe shall be provided for use
             authority and this chapter.                          during construction. Such standpipes shall be installed prior
             [BG] 1503.2  Obstructions. Construction materials and  to construction exceeding 40 feet (12  192 mm) in height
             equipment shall not be placed or stored so as  to obstruct  above the lowest level of fire department vehicle access. Such
             access to fire hydrants, standpipes, fire or police alarm boxes,  standpipes shall be provided with fire department hose con-
             catch basins or manholes, nor shall such material or equip-  nections at locations adjacent to stairways, complying with
             ment be located within 20 feet (6096 mm) of a street intersec-  Section 1505.1. As construction progresses, such standpipes
             tion, or placed so as to obstruct normal observations of traffic  shall be extended to within one floor of the highest point of
             signals or to hinder the use of public transit loading plat-  construction having secured decking or flooring.
             forms.
                                                                  [F] 1506.2 Buildings being demolished. Where a building or
             [BG] 1503.3 Utility fixtures. Building materials,  fences,  portion of a building is being demolished and a standpipe is
             sheds or any obstruction of any kind shall not be placed so as  existing within such a building, such standpipe shall be main-
             to obstruct free approach to any fire hydrant, fire department  tained in an operable condition so as to be available for use
             connection, utility pole, manhole, fire alarm  box, or catch  by the fire department. Such standpipe shall be demolished
             basin, or so as to interfere with the passage of water in the  with the building but shall not be demolished more than one
             gutter. Protection against damage shall be provided to such
             utility fixtures during the progress of the work, but sight of  floor below the floor being demolished.
             them shall not be obstructed.                        [F] 1506.3 Detailed  requirements. Standpipes shall  be
                                                                  installed in accordance with the provisions of Chapter 9 of
                               SECTION 1504                       the International Building Code.
                           FIRE EXTINGUISHERS                        Exception: Standpipes shall be either temporary or per-
             [F] 1504.1 Where required. Structures under construction,  manent in nature, and with or without a water supply, pro-
             alteration or demolition shall be provided with not fewer than  vided that such standpipes conform to the requirements of
             one approved portable fire extinguisher in accordance with  Section 905 of the  International Building  Code as to
             Section 906 of the International Fire Code and sized for not  capacity, outlets and materials.
             less than ordinary hazard as follows:
               1. At each stairway on all floor levels where combustible
                  materials have accumulated.                                       SECTION 1507
                                                                          AUTOMATIC SPRINKLER SYSTEM
               2. In every storage and construction shed.
               3. Additional portable fire extinguishers shall be provided  [F] 1507.1  Completion before occupancy. In buildings
                  where special hazards exist, such as the storage and use  where an automatic sprinkler system is required by this code
                  of flammable and combustible liquids.           or the  International Building  Code, it shall be  unlawful  to
             [F] 1504.2 Fire hazards. The provisions of this code and of  occupy any portions of a building or structure until the auto-
             the International Fire Code shall be strictly observed to safe-  matic sprinkler system installation has been tested and
             guard against all fire hazards attendant upon construction  approved, except as provided in Section 110.3.
             operations.                                          [F] 1507.2 Operation of valves. Operation of sprinkler con-
                                                                  trol valves  shall be  permitted  only by properly authorized
                               SECTION 1505                       personnel and shall be accompanied by notification of duly
                            MEANS OF EGRESS                       designated parties. When  the  sprinkler protection is being
                                                                  regularly turned off and on to facilitate connection of newly
             [BE] 1505.1 Stairways required. Where building construc-
             tion exceeds 40 feet (12 192 mm) in height above the lowest  completed segments,  the  sprinkler control valves  shall be
             level of fire department vehicle access, a temporary or perma-  checked at the end of each work period to ascertain that pro-
             nent stairway shall be provided. As construction progresses,  tection is in service.
             such stairway shall be  extended to  within one floor of the
             highest point of construction having secured decking or floor-
             ing.                                                                   SECTION 1508
                                                                                   ACCESSIBILITY
             [F]  1505.2 Maintenance of means  of  egress. Means  of
             egress and required accessible means of egress shall be main-  [BE] 1508.1 Construction sites. Structures, sites, and equip-
             tained at all times during construction, demolition, remodel-  ment directly associated with the actual process of construc-
             ing or alterations and additions to any building.    tion, including but  not limited to scaffolding, bridging,
               Exception: Existing means of egress need not be main-  material hoists, material storage, or construction trailers are
               tained where  approved temporary means of  egress and  not required to be accessible.
               accessible means of egress systems and facilities are pro-
               vided.
                                                                                    SECTION 1509
                               SECTION 1506                            WATER SUPPLY FOR FIRE PROTECTION
                               STANDPIPES                         [F] 1509.1 When required. An approved water supply for
             [F] 1506.1 Where required. In buildings required to have  fire protection, either temporary or permanent, shall be made
             standpipes by Section 905.3.1 of the International Building  available as soon as combustible material arrives on the site.

             2018 INTERNATIONAL EXISTING BUILDING CODE ®                                                          77
  Copyrighted © 2017 by, or licensed to, ICC (ALL RIGHTS RESERVED); licensed to UL, LLC pursuant to License Agreement with ICC. No further reproductions authorized or distribution authorized.
  ANY UNAUTHROIZED REPRODUCTION OR DISTRIBUTION IS A VIOLATION OF THE FEDERAL COPYRIGHT ACT AND THE LICENSE AGREEMENT; AND SUBJECT TO CIVIL AND CRIMINAL PENALTIES THEREUNDER.
   91   92   93   94   95   96   97   98   99   100   101