Page 96 - ICC IEBC 2018
P. 96
CONSTRUCTION SAFEGUARDS
comply with the provisions of the applicable governing Code, not less than one standpipe shall be provided for use
authority and this chapter. during construction. Such standpipes shall be installed prior
[BG] 1503.2 Obstructions. Construction materials and to construction exceeding 40 feet (12 192 mm) in height
equipment shall not be placed or stored so as to obstruct above the lowest level of fire department vehicle access. Such
access to fire hydrants, standpipes, fire or police alarm boxes, standpipes shall be provided with fire department hose con-
catch basins or manholes, nor shall such material or equip- nections at locations adjacent to stairways, complying with
ment be located within 20 feet (6096 mm) of a street intersec- Section 1505.1. As construction progresses, such standpipes
tion, or placed so as to obstruct normal observations of traffic shall be extended to within one floor of the highest point of
signals or to hinder the use of public transit loading plat- construction having secured decking or flooring.
forms.
[F] 1506.2 Buildings being demolished. Where a building or
[BG] 1503.3 Utility fixtures. Building materials, fences, portion of a building is being demolished and a standpipe is
sheds or any obstruction of any kind shall not be placed so as existing within such a building, such standpipe shall be main-
to obstruct free approach to any fire hydrant, fire department tained in an operable condition so as to be available for use
connection, utility pole, manhole, fire alarm box, or catch by the fire department. Such standpipe shall be demolished
basin, or so as to interfere with the passage of water in the with the building but shall not be demolished more than one
gutter. Protection against damage shall be provided to such
utility fixtures during the progress of the work, but sight of floor below the floor being demolished.
them shall not be obstructed. [F] 1506.3 Detailed requirements. Standpipes shall be
installed in accordance with the provisions of Chapter 9 of
SECTION 1504 the International Building Code.
FIRE EXTINGUISHERS Exception: Standpipes shall be either temporary or per-
[F] 1504.1 Where required. Structures under construction, manent in nature, and with or without a water supply, pro-
alteration or demolition shall be provided with not fewer than vided that such standpipes conform to the requirements of
one approved portable fire extinguisher in accordance with Section 905 of the International Building Code as to
Section 906 of the International Fire Code and sized for not capacity, outlets and materials.
less than ordinary hazard as follows:
1. At each stairway on all floor levels where combustible
materials have accumulated. SECTION 1507
AUTOMATIC SPRINKLER SYSTEM
2. In every storage and construction shed.
3. Additional portable fire extinguishers shall be provided [F] 1507.1 Completion before occupancy. In buildings
where special hazards exist, such as the storage and use where an automatic sprinkler system is required by this code
of flammable and combustible liquids. or the International Building Code, it shall be unlawful to
[F] 1504.2 Fire hazards. The provisions of this code and of occupy any portions of a building or structure until the auto-
the International Fire Code shall be strictly observed to safe- matic sprinkler system installation has been tested and
guard against all fire hazards attendant upon construction approved, except as provided in Section 110.3.
operations. [F] 1507.2 Operation of valves. Operation of sprinkler con-
trol valves shall be permitted only by properly authorized
SECTION 1505 personnel and shall be accompanied by notification of duly
MEANS OF EGRESS designated parties. When the sprinkler protection is being
regularly turned off and on to facilitate connection of newly
[BE] 1505.1 Stairways required. Where building construc-
tion exceeds 40 feet (12 192 mm) in height above the lowest completed segments, the sprinkler control valves shall be
level of fire department vehicle access, a temporary or perma- checked at the end of each work period to ascertain that pro-
nent stairway shall be provided. As construction progresses, tection is in service.
such stairway shall be extended to within one floor of the
highest point of construction having secured decking or floor-
ing. SECTION 1508
ACCESSIBILITY
[F] 1505.2 Maintenance of means of egress. Means of
egress and required accessible means of egress shall be main- [BE] 1508.1 Construction sites. Structures, sites, and equip-
tained at all times during construction, demolition, remodel- ment directly associated with the actual process of construc-
ing or alterations and additions to any building. tion, including but not limited to scaffolding, bridging,
Exception: Existing means of egress need not be main- material hoists, material storage, or construction trailers are
tained where approved temporary means of egress and not required to be accessible.
accessible means of egress systems and facilities are pro-
vided.
SECTION 1509
SECTION 1506 WATER SUPPLY FOR FIRE PROTECTION
STANDPIPES [F] 1509.1 When required. An approved water supply for
[F] 1506.1 Where required. In buildings required to have fire protection, either temporary or permanent, shall be made
standpipes by Section 905.3.1 of the International Building available as soon as combustible material arrives on the site.
2018 INTERNATIONAL EXISTING BUILDING CODE ® 77