Page 82 - Engine IQflip'21
P. 82

Mode of Operation




                     Parallel with customer Gas engine/Diesel set



                      Requirement for island parallel operation with customer                                 Active load sharing (kW)
                      engines:                                                                                Engine speed regulator with adjustable quadrature droop kit
                       The customer engines have to fulfill some preconditions:                               and similar speed response time! Operation of the complete
                                                                                                              system is possible with droop or load sharing line-(fix
                      400V Alternator winding system                                                          adjustment during set up through commission-ing stuff
                      INNIOJ Generator with 2/3 pitch main stator winding.                                    according site requirement).  INNIO Jenbacher provides
                      If customer generator (400V) is not fitted with 2/3 pitch main                          terminals (+IS) for a load sharing signal 0–5V or 4–16mA = 0–
                      stator                                                                                  100 % from the customer.
                      winding a neutral choke has to be fitted to the customer
                      generator-scope                                                                         INNIOJ alternator AVR has U/f function, if customer alternator
                      of supply from customer – if star points are connected                                  AVR don´t have same characteristic that feature has to be
                      together –                                                                              disabled! Possible operation functions of complete system
                      to avoid higher neutral current.                                                        (one selector switch on the Interlock Panel):

                      11KV Alternator winding system                                                              Power mode function of the running INNIOJ engines with
                      INNIOJ Generator with 5/6 pitch main stator winding.                                    •   customer engines only if the customer running engines
                      Star point is normally not grounded – delivery and control of a                             have actual twice as much power as INNIOJ because of
                      necessary grounding (NGR) system according customer SLD                                     stability reasons.
                      is scope of supply from customer!
                                                                                                                  −   Speed mode:
                      Reactive load sharing (kvar)                                                                    A) with load sharing line (Customer signal 0–5V or 4-16mA =
                      Generator with “voltage droop“ for reactive load sharing –                                      0–100%PN)
                      „adjustable quadrature droop kit“.                                                              B) with droop if no load sharing line is available! (e.g.:
                                                                                                                      mechanical speed governor)


                                                                                                                  Signals according interface list from INNIOJ have to be
                                                                                                                  exchanged between
                                    All rights reserved      May 19                                               the customer engine and the INNIO Jenbacher gas engine
                                                                                                                  to ensure safe operation conditions!
   77   78   79   80   81   82   83   84   85   86   87