Page 77 - Engine IQflip'21
P. 77

Blackout start


                   (Mains parallel & island mode)




                   Resynchronization

                                                                                                             Function


                                                                                                             First closing of GCB to black (“dead”)  busbar





                                                                                                             Procedure

                                                                                                             1.) Engine ready to start (preheated, no failure)


                                                                                                             2.) Mains/Grid Failure (MCB open)

                                                                                                             3.) Engine commences start preparation


                                                                                                             4.) Engine runs up to rated speed, GCB is closed
                                                                                                                 (different procedures possible)


                                                                                                             5.) Engine runs in island mode (GCB closed)



                                           Consumer load         Gas engines






                                    All rights reserved      May 19
   72   73   74   75   76   77   78   79   80   81   82