Page 150 - Saber® Installation & Startup
P. 150
INSTALLATION & STARTUP
Chapter 9 Water Softener
Model 213S OD / WA and WB Connections
Installing the Brine Valve
1) After the adjustments have been made to the adjuster tub and the float cup, the brine valve assembly must be installed in the
brine drum. Locate the brine valve in the brine well so that the bent tube is along the back of the brine well away from the
brine drum wall. The bent tube snaps into a notch and extends from the brine drum about 1".
Do not drop the brine valve into the drum!
Dropping may lower the float cup, resulting in an improper setting.
1/2” barbed
overflow fitting
(typical on all
storage tanks)
Plastic push-on
fitting (typical on all
storage tanks)
9-6 Belanger, Inc. * PO BOX 5470 * Northville, MI 48167-5470 * Ph (248) 349-7010 * Fax (248) 380-9681 1MANUL290