WEEKLY
                              • Clearing of switch room & riser rooms.
             Switch           • Cleaning of cable trench / condition of cable trench (ensure clean, water free
             Room                and slab cover – ok).
           Including          • Ensure anti vermin wire mesh is in good condition – repair if damaged.
          Riser Room          • Ensure no water flowing into Switch Room / Riser room – repair if leakage /
                                 damaged.
                              • Ensure wiring and electrical fittings, power points, light fittings and exhaust fans
                                 working properly.
                              • Ensure duct seals is in good condition – repair if damage.




                               WEEKLY
                              • Ensure all indicator light, selector switches, voltmeter, ammeter, power factor
                                 meter working properly – replace if faulty.
                              • Record readings for maximum current, voltage, power factor, etc into the log
         Main Switch             book and take necessary action.
            Board /           • Ensure cable insulation, cable box, cable terminations and other related
          Sub-Switch             connections in good condition. Replace / repair if required.
            Boards             MONTHLY


                              • Ensure earthing system and all terminations, connections working properly –
                                 repair / replace if faulty.
                              • Check copper busbars and ensure that is in good condition – replace / repair if
                                 damage.




                                 PER 3 MONTHS

                              • Check condition and clean / vacuum internal part of the DB.
                              • Ensure that DB no. / name plate, “Danger” and updated schematic diagram are
                                 available and readable / visible.
           Distribution       • Inspect and ensure spares ways are available in the DB.
           Board (DB)         • Tripping test for MCB – ensure that is working perfectly – replace if faulty.

                                     YEARLY
                              • Retighten fuse handle – replace if necessary.
                              • Test on continuity of fuses – replace if faulty.
                              • Clean internal part of the distribution board.



                                     YEARLY

              Fuse            • Continuity test on fuse – replace with correct rating if damage / faulty.
           Switches /         • Retighten fuse carriers.
             Switch           • Clean contacts with clean dry cloth to ensure good contact.
             Fuses            • Retighten all connections / termination to prevent from any sparking when
                                 loaded.
                              • Inspect cover for any damage – replace or repair if damage.
                              • Ensure switch handle is in good condition, replace if damage.