Page 61 - kursus eBook
P. 61

DRAFT GUIDELINE ON DOMESTIC GAS PIPING SYSTEM


                   Pipe support

                   The  piping  system  must  be  supported  to  avoid  the  external  strength  such  as  vibration,
                   thermal shrinkage and must be installed at a location where maintenance work can be done
                   easily.
                   Gas piping shall be supported with the proper size pipe hooks, metal pipe straps, bands or
                   hangers.

                   The supports must be of adequate strength and quality, and located at proper intervals, so
                   that the piping cannot be moved accidentally from the installed position.

                   The  building  structure  shall  not  be  weakened  by  the  installation  of  any  gas  piping.  Gas
                   piping shall not be supported by other piping.

                   Spacing  of  supports  in  gas  piping  installations  shall  not be greater than as shown below
                   (taken from table 2 of MS 930):

                                  Steel Pipe                        Nominal
                                 Nominal Size       Spacing of      Size of         Spacing of
                                 of Pipe            Supports        Tubing          Supports
                                 (Inches)           (Feet)          (Inch OD)       (Feet)
                                 1/2                 6               1/2             4
                                  3/4 or 1           8               5/8 or 3/4      6
                                  1 1/4 or
                                 larger             10               7/8 or 1       8
                                 (horizontal)
                                  1 1/4 or           Every
                                 larger
                                 (vertical)         floor level


                   Pipe Tracer Wire

                   For polyethylene (PE) underground gas piping installation, a tracer wire is installed along the
                   entire length of gas pipe for the purpose of locating the gas pipe from aboveground using a
                   pipe locator.
                   The tracer wire should be installed around the pipe surface and the wire ends should be led
                   to aboveground, at appropriate intervals, where the discontinuity can be detected easily.

                   An insulated copper wire of at least 4 mm should be used as tracer wire.

                   Clearance from Other Buried Facilities

                   When a gas pipe runs close to some other services, contact between them shall be
                   prevented by segregation or other means. Requirements for clearance (parallel and cross
                   layout distances) from other buried facilities is as shown in the figure below:

                   For polyethylene pipe installation, ample clearance must be provided to separate such pipe
                   from any heat source in order to assure that the surface temperature of the pipe does not
                             o
                   exceed 35 C





                                                                                                           21
   56   57   58   59   60   61   62   63   64   65   66