Page 107 - Wago_AutomationTechnology_Volume3_2015_US.pdf
P. 107
3
105
I/O
modules
FIELDBUS INTERFACE 1 5 24 V 24 V
24 V /0 V
10 nF
5 V 5 V ELECTRONICS
0 V
6
2
FIELDBUS INTERFACE 24 V 24 V INTERFACE
FIELDBUS
3 7 0 V INTERFACE 1) 2)
FIELDBUS
ELECTRONICS 4 8 0 V 10 nF 1) 15 nF
2) 1 MΩ
750-804
3.2
Technical Data General Specifications
Number of I/O modules 64 Operating temperature 0 °C ... +55 °C
Max. input process image 64 bytes Wire connection CAGE CLAMP ®
Max. output process image 64 bytes Cross sections 0.08 mm² ... 2.5 mm² / AWG 28 ... 14
Max. input variables 64 bytes Strip lengths 8 ... 9 mm / 0.33 in
Max. output variables 64 bytes Dimensions (mm) W x H x L 51 x 65 x 100
Configuration automatic Height from upper-edge of DIN 35 rail
Program memory 128 Kbytes Weight 200 g
Data memory 64 Kbytes Storage temperature -25 °C ... +85 °C
Non-volatile memory (retain) 8 Kbytes Relative air humidity (no condensation) 95 %
Cycle time < 3 ms for 1,000 statements / Vibration resistance acc. to IEC 60068-2-6
256 dig. I/Os Shock resistance acc. to IEC 60068-2-27
Power supply 24 VDC (-25 % ... +30 %) Degree of protection IP20
Max. input current (24 V) 500 mA EMC immunity of interference acc. to EN 61000-6-2
Power supply efficiency 87 % EMC emission of interference acc. to EN 61000-6-4
Internal current consumption (5 V) 400 mA
Total current for I/O modules (5 V) 1600 mA
Isolation 500 V system/supply
Voltage via power jumper contacts 24 VDC (-25 % ... +30 %)
Current via power jumper contacts (max.) 10 A DC