Page 29 - Parker - AC890/AC890PX series
P. 29

High Power Modular AC Drive


          AC890PX Series
          150 - 600 HP/110 - 400kW


          Alternative Input Power Configurations


          Active Front-End (AFE) Version - Energy regeneration with low harmonic distortion

                                                                  •  Fully line regenerative drive
                                                                  •  Continuous duty at full torque - motoring
                          Input                                      or braking
                          Power                                   •  Negligible power line harmonics - meets
                          Entry                  AC890 control       IEEE519
                                                 modules          •  Unity power factor
                                                                  •  Compact 3 bay (1600 mm) enclosure
                                     Motor
                           AFE      Inverter                      •  Grid Tie models also available
                          Power      Power
                          Frame                                                       Active
              LCL                    Frame                                            Bridge    Inverter
           Harmonic                                                      LCL Filter
              Line
              Filter                              Motor Power                                                M
                                                  Connections

                                                                                  POWER FLOW



          The modular design of the AC890PX makes it easy to configure parallel input modules and multi-phase configurations. By using 12-pulse
          or 18-pulse configurations, harmful line harmonics can be greatly reduced. Or, for the ultimate in harmonic abatement, an Active Front
          End (AFE) may be selected. The typical AC drive has six rectifiers in a three phase bridge configuration, and is commonly referred to as a
          “6-pulse” configuration. A 12-pulse drive contains two sets of six rectifiers, an 18-pulse drive, three sets of six rectifiers and so on. If the AC
          power connected to each set of rectifiers is “phase shifted”, then some of the harmonics produced by one set of rectifiers will be opposite
          in polarity from the harmonics produced by the other set of rectifiers. The two (or three) wave forms effectively cancel each other out. To
          provide the phase shifted AC power, a transformer with multiple secondary windings is used.

          Alternative Input Supplies                                      Active Front End (AFE)


















                                                                            4-Quadrant Regenerative
                 12-Pulse Input                   18-Pulse Input                 Drive with AFE