Page 67 - Wieland - Safety: Safe system solutions for automation technology
P. 67

safe relay









        Overview of devices | Part numbers
         Type               Rated voltage       Terminals                             Part no.          Std. Pack
         SNE 4003K-A        24 V DC             Screw terminals, pluggable            R1.188.1340.0        1













        Technical data

         Function                                           Emergency stop expansion relay
         Function display                                   2 LEDs, green
         Power supply circuit
                                     B1/B2, B3/B4           24 V DC
         Rated voltage U N
         Rated consumption           24 V DC                1.2 W
         Operating voltage range U B                        0.63 - 1.25 x U N
         Electrical isolation supply circuit - control circuit  no
         Control circuit
         Input current / peak current  B1/B2, B3/B4         50 mA / 500 mA
                                                            < 40 ms
         Response time t A1 / t A2
         Recovery time t W                                  ≤ 40 ms                                                   relay
                                                            < 20 ms
         Release time t R
                                                            < 1 ms
         Permissable test pulse time t TP                                                                             safe
         Max. resistivity, per channel  1)                  ≤ (5 + (1.6 x U B / U N  - 1) x 100) Ω
         Output circuit
         Enabling paths              13/14, 23/24, 33/34    normally open contact
         Signaling paths             41/42                  normally closed contact
         Contact assignment                                 forcebly guided
         Contact type                                       Ag-alloy, gold-plated
         Rated switching voltage     enabling- / signaling path  230 V AC
                                     Y1/Y2                  230 V AC
                                     enabling- / signaling path     6 A / 2 A
         Max. thermal current I th
                                     Y1/Y2                  2 A
         Max. total current I  of all current path  (Tu = 55 ºC)  9 A²
                     2
         Application category (NO)   AC-15                  U e 230 V, I e 3 A
                                     DC-13                  U e 24 V, I e 2,5 A
         Short-circuit protection (NO), lead fuse / circuit breaker  6 A class gG / melting integral < 100 A²s
         Mechanical life                                    10  switching cycles
                                                             7
         General data
         Creepage distances and clearances between the circuits  EN 60664-1
         Protection degree according to EN 60529 (housing / terminals)  IP40 / IP20
         Ambient temperature / storage temperature          -25 ºC - +55 ºC / -25 ºC - + 75 ºC
         Wire ranges screw terminals,    fine-stranded / solid  1 x 0.2 mm² – 2.5 mm² / 2 x 0.2 mm² – 1.0 mm²
                                     fine-stranded with ferrules  1 x 0.25 mm² – 2.5 mm² / 2 x 0.25 mm² – 1.0 mm²
         Permissible torque                                 0.5 - 0.6 Nm
         Wire ranges push-in terminals                      1 x 0.25 mm² – 1.5 mm²
         Weight                                             0,21 kg
         Standards                                          EN ISO 13849-1, EN 62061
         Approvals                                          DGUV, cULus, CCC, GOST R
         1)  If two-channel devices are installed as single channel, the value is halved.










                                                                                                                 67
   62   63   64   65   66   67   68   69   70   71   72