Page 150 - Wagp_InterfaceElectronic_Volume4_2015_US.pdf
P. 150
2 Rail-Mounted Terminal Blocks with Optocoupler
148
Optocoupler Optocoupler
Input: 5 VDC Input: 5 VDC
Output: 5 VDC / 500 mA/10 kHz Output: 12 VDC / 500 mA/10 kHz
Positive switching Positive switching
56 mm/2.2 in
91 mm/3.58 in
A2 A2
— 0 V — 0 V
R L R L
A A
A1 A1
+ +5 V + +12 V
Description Item No. Pack. Item No. Pack.
I N
V N
Unit V N I N Unit
Rail-mounted terminal block with optocoupler, 5 VDC 8 mA 859-750 1 5 VDC 8 mA 859-751 1
for DIN 35 rail
Technical Data Accessories see page 156 Accessories see page 156
Control circuit:
Input voltage range (low level) 0 ... 1 VDC 0 ... 1 VDC
Input voltage range (high level) 4 ... 6.25 VDC 4 ... 6 VDC
Load circuit:
Output voltage range 4 ... 6.25 VDC 8 ... 18 VDC
Max. continuous current 500 mA 500 mA
Peak output current 4 A 4 A
Turn-on time < 15 μs < 15 μs
Turn-off time < 30 μs < 30 μs
Max. switching frequency 10 kHz 10 kHz
Max. voltage drop at output 1.2 V 1.2 V
Reverse voltage transistor/triac 80 V 80 V
General specifications:
Dielectric strength, control/load circuit (AC, 1 min) 2.5 kV rms 2.5 kV rms
Ambient operating temperature -25 °C ... +40 °C -25 °C ... +40 °C
Storage temperature -40 °C ... +70 °C -40 °C ... +70 °C
Dimensions (mm) W x H x L 6 x 56 x 91 6 x 56 x 91
Height from upper-edge of DIN 35 rail Height from upper-edge of DIN 35 rail
Wire connection CAGE CLAMP ® CAGE CLAMP ®
Cross sections 0.08 mm² … 2.5 mm² / AWG 28 … 14 0.08 mm² … 2.5 mm² / AWG 28 … 14
Strip length 5 … 6 mm / 0.2 … 0.24 in 5 … 6 mm / 0.2 … 0.24 in