Optocoupler Optocoupler
Input: 24 VDC Input: 5 V DC
Output: 3 ... 30 VDC / 500 mA Output: 230 V AC/0.5 A
Changeover contact output
2
Continuous current
I (mA)
500
300
100
0 10 30 50 70 ϑ (°C)
Ambient operating temperature
Derating
12
A2
1
R L
11
A1 14 R L
Description Item No. Pack. Item No. Pack.
I N
V N
Unit V N I N Unit
Rail-mounted terminal block with optocoupler, 24 VDC 5.3 mA 859-732 1 5 V DC 7.7 mA 859-902 1
for DIN 35 rail
Technical Data Accessories see page 156 Accessories see page 156
Control circuit: 8
Input voltage range (low level) 0 ... 5 VDC 0 ... 1 VDC
Input voltage range (high level) 15 V ... 42 VDC 4 ... 6.25 VDC
Load circuit:
Output voltage range 3 ... 30 VDC 24 V ... 260 V AC (50 Hz ... 60 Hz)
Max. continuous current 500 mA 500 mA
Peak output current 4 A 30 A
Turn-on time 25 μs 10 ms
Turn-off time 150 μs 10 ms
Max. switching frequency 1.5 kHz
Max. voltage drop at output 1.5 V 1.2 V
Reverse voltage transistor/triac 80 V 600 V
General specifications:
Dielectric strength, control/load circuit (AC, 1 min) 3.75 kV rms 2.5 kV rms
Ambient operating temperature -25 °C ... +55 °C -25 °C ... +55 °C
Storage temperature -25 °C ... +70 °C -40 °C ... +70 °C
Dimensions (mm) W x H x L 6 x 56 x 91 6 x 56 x 91
Height from upper-edge of DIN 35 rail Height from upper-edge of DIN 35 rail
Wire connection CAGE CLAMP ® CAGE CLAMP ®
Cross sections 0.08 mm² … 2.5 mm² / AWG 28 … 14 0.08 mm² … 2.5 mm² / AWG 28 … 14
Strip length 5 … 6 mm / 0.2 … 0.24 in 5 … 6 mm / 0.2 … 0.24 in
Standards/specifications EN 60664-1; UL 508 EN 60664-1