           Switched-Mode Power Supply, 1-Phase                                                                     5

                   ®
           EPSITRON  PRO Power                                                                                      277







                                                                                            Stand-by
                                                                                                 DC O.K.
                                                                                           L
                                                                                                   DC+
                                                                                           N       DC+
                                                                                                   DC -
                                                                                                   DC -










           • Primary switch mode power supply unit with PowerBoost and TopBoost                              Pack.
           • Stand-by input for switching off the output and minimizing power   Description  Item No.        Unit
            consumption                                         Switched-Mode Power Supply,   787-833        1
           • DC OK contact for output monitoring                48 V DC / 5 A
           • Parallel operation, series connection possible                                                         5
           • Prepared for class I equipment
           • Natural convection cooling when horizontally mounted
           • Enclosed for use in switchgear cabinets
           • Electrically isolated output voltage (SELV) acc. to EN 60950-1/UL 60950

           Technical Data                                       Technical Data

           Input:                                               Environmental requirements:
            Nominal input voltage Vi nom  110 ... 240 VAC         Ambient operating temperature  -25 °C ... +70 °C
            Input voltage range     85 ... 264 VAC; 120 ... 350 VDC  Storage temperature  -25 °C ... +85 °C
            Input voltage derating  -1.5 % / V AC < 110 VAC       Rel. humidity           30 % ... 85 % (no condensation)
            Frequency               50 Hz ... 60 Hz               Derating                -3 % / K (> +50 °C)
            Input current Ii        1.2 A at 230 VAC and 5 ADC    Degree of pollution     2 (acc. to EN 50178)
            Discharge current       1 mA typ.                     Climatic category       3K3 (acc. to EN 60721)
            Inrush current          < 8 A (active inrush current limitation)  Safety and protection:
            Mains failure hold-up time  20 ms typ. at 230 VAC     Test voltage pri.-sec./ pri.-gr. / sec.-gr.  4.2 kV DC / 2.2 kV DC / 0.7 kV DC
           Output:                                                Protection class        Prepared for class I equipment
            Nominal output voltage Vo nom  48 VDC (SELV)          Degree of protection    IP20 (acc. to EN 60529)
            Output voltage range    33 ... 52 VDC adjustable      Overvoltage protection  via varistor at primary circuit
            Output current Io       5 A at 48 V DC                Short circuit protection  yes
            PowerBoost              10 ADC (for 4 s); 7.5 ADC (for 8 s)  No-load proof    yes
            TopBoost                30 ADC (for 25 ms)            Feedback voltage        max. 63 VDC
            Factory preset          48 VDC                        Parallel operation      yes
            Adjustment accuracy     1%                            Series connection       yes
            Residual ripple         < 70 mV (peak-peak)         Connection and type of mounting:
            Current limitation      1.1 x Io typ.                 Wire connection         Input/Output: WAGO 231 Series
            Overload behavior       TopBoost / PowerBoost /Constant current               Signalising: WAGO 733 Series
            Operational indication  LED green (DC O.K.), LED red (error)  Cross sections  Input/Output:
            Signaling               Relay contact DC O.K. (changeover                     0.08 mm² ... 2.5 mm² / AWG 28 ... 12
                                    contact)                                              Signalising:
           Efficiency / power losses:                                                     0.08 mm² ... 0.5  mm² /  AWG 28 ... 20
            Efficiency              91 % typ.                     Strip lengths           Input/Output: 8 ... 9 mm / 0.33 in
                                    0.8 W (stand-by) / 7.4 W (no load)  /                 Signalising: 5 ... 6  mm / 0.22 in
            Power loss P V
                                    21.6 W (rated load)           Type of mounting        DIN-rail mounting (EN 60715) in
           Fuse protection:                                                               2 positions
            Internal fuse           T 6.3 A / 250 V             Dimensions and weight:
            External fuse           Circuit breakers 6 A, 10 A, 16 A,   Dimensions (mm) W x H x L  57 x 163 x 179
                                    characteristic: B or C                                (incl. female connector)
                                    An external DC fuse is required for the DC            Length from upper-edge of DIN 35 rail
                                    input voltage                 Weight                  1475 g
                                                                Standards and approvals:
                                                                  Standards/Specifications  EN 60950, EN 61204-3,
                                                                                          UL 60950, UL 508