Page 65 - Wagp_InterfaceElectronic_Volume4_2015_US.pdf
P. 65

1



                                                                                                                    63
                                              Suppressor module,
                                              pluggable,
                                              for 788 and 858 Series Relay Sockets                                  1












           Note: To guarantee safe operation, residual voltages (due
           to the cable capacitance of long connection lines or
           leakage currents of semi-conductor switches and their
           protective circuits) must be lower than the release voltage
           of the relays.
           For DC relays, the release voltage is specified with ≤ 5 % of
           the nominal voltage; for AC relays, it is 15 % of the nominal
           voltage (acc. to VDE 0435).
           The relay may not reset if a high residual voltage exists.
           Depending on the reason for the residual voltage,
           changing the cable routing or a parallel connection of an
           RC element could remedy this situation.


           Description                                     Item No.        Pack.
                                                                           Unit
           Suppressor module for miniature switching relay  788-148        50








           Technical Data

           Operating data:
            Operating voltage                         max. 230 VAC, 50 ... 60 Hz
            Operating current                          3.6 mA at 115 VAC, 50 Hz
                                                       7.2 mA at 230 VAC, 50 Hz
           Module's characteristics:
            Resistor                                        470 Ω
            Capacity                                        100 nF
           General specifications:
            Ambient operating temperature                -25 °C ... +70 °C
            Storage temperature                          -40 °C ... +70 °C
            Dimensions (mm) W x H x L                      15 x 15 x 10
            Standards/specifications                       EN 60664-1
   60   61   62   63   64   65   66   67   68   69   70