1 Sockets with Industrial Relay
60
Relay sockets with industrial relay Relay socket with industrial relay
Coil voltage: 24 V, 48 V, 110 V, 220 V DC Coil voltage: AC 230 V
2 changeover contacts 2 changeover contacts
Switching current (A) 50 DC resistive load
12
10
2 5
1
0.5
0.1
10 20 30 4050 100 200 300
Switching voltage (V)
DC load limit curve
14 14
A1 A1
+ 11 11
12 12
24 24
21 21
A2 A2
- 22 22
Description Item No. Pack. Item No. Pack.
I N
V N
Unit V N I N Unit
Socket with industrial relay, 24 VDC 37.5 mA 858-324 1 230 VAC 11 mA 858-528 1
for DIN 35 rail 48 VDC 18.5 mA 858-325 1
110 VDC 8.1 mA 858-327 1
220 VDC 4.1 mA 858-328 1
Technical Data Accessories see pages 61 … 65 Accessories see pages 61 … 65
Coil:
Input voltage range V N -20 % ... +10 % V N -20 % ... +10 %
Contacts:
Contact material AgNi AgNi
Max. continuous current 2 x 12 A 2 x 12 A
Max. make current 24 A (4 s ) 24 A (4 s )
Max. switching voltage 250 VAC 250 VAC
Max. switching power (resistive) 2 AC x 3000 VA, DC see load limit curve 2 AC x 3000 VA, DC see load limit curve
Recommended minimum load 5 V / 5 mA / 0.3 W 5 V / 5 mA / 0.3 W
Pull-in/drop-out/bounce time typ. 13ms / 3ms / - 10ms / 8ms / -
7
7
Mechanical life 2 x 10 switching operations 2 x 10 switching operations
General specifications:
Nominal voltage to EN 60664-1 250 V / 2.5 kV / 2 250 V / 2.5 kV / 2
Dielectric strength, contact-coil (AC, 1 min) 2.5 kV rms 2.5 kV rms
Dielectric strength open contact (AC, 1 min) 1.5 kV rms 1.5 kV rms
Dielectric strength contact-contact (AC, 1 min) 2.5 kV eff 2.5 kV eff
-40 °C ... +70 °C -40 °C ... +70 °C
Ambient operating temperature at V N
Storage temperature -40 °C ... +70 °C -40 °C ... +70 °C
Dimensions (mm) W x H x L 31 x 73 x 97 31 x 73 x 97
Height from upper-edge of DIN 35 rail Height from upper-edge of DIN 35 rail
®
®
Wire connection CAGE CLAMP S CAGE CLAMP S
Cross sections 2 x 0.34 mm² ... 2 x 1.5 mm² / 2 x 0.34 mm² ... 2 x 1.5 mm² /
1 x 2.5 mm²/ 1 x 2.5 mm²/
AWG 22 ... 16 AWG 22 ... 16
Strip length 9 … 10 mm / 0.35 … 0.39 in 9 … 10 mm / 0.35 … 0.39 in
Standards/specifications EN 61810-1; EN 60664-1 EN 61810-1; EN 60664-1