Page 86 - Wagp_InterfaceElectronic_Volume4_2015_US.pdf
P. 86
1 Pluggable Modules - Relays
84
Relay with 1 changeover contact –
Contact hard gold plated
Module width 15 mm / 0.591 in
11 11
* In order to prevent the gold layer from being damaged, A1 A1
+ ~
30 VDC switching voltages and 50 mA currents shall not
be exceeded.
Higher switching power leads to evaporation of the gold
A2 A2
layer. The resulting deposits in the housing may reduce the – 12 ~ 12
A2 A2 14
service life. – 14 ~
Description Item No. Pack.
Unit
V N
I N
Switching relay module 24 V DC 21.8 mA 286-394 1
48 V DC 11.4 mA 286-395 1
24 V AC/DC 21.8 mA 286-594 1
Technical Data Accessories see pages 99 … 100
Contact material AgNi + Au
Max. switching voltage 250 VAC *
Max. continuous current 1 A *
Pull-in/drop-out/bounce time typ. 9ms / 3ms / ms
Dielectric strength contact-coil (AC, 1 min) 4 kV
Nominal voltage acc. to VDE 0110 Part 1/4.97, 250 V / 4 kV / 2
IEC 60664-1
6
Mechanical life 30 x 10 switching operations
Mechanical life at max. load (resistance) 1 x 10 switching operations
5
Ambient operating temperature -25 °C ... +40 °C
Accessories Item No. Pack. Item No. Pack.
Unit Unit
Terminal block for pluggable modules, with 2-
conductor terminal blocks, orange separator ➊ 17 mm / 0.669 in wide 280-619 1
with 4-conductor terminal blocks, orange separator ➋ 17 mm / 0.669 in wide 280-609 1
with 4-conductor terminal blocks, marker plate ➋ 20 mm / 0.787 in wide 280-763 1
wire range 0.08 mm² ... 2.5 mm² / AWG 28 ... 14;
stripped length 8 ... 9 mm / 0.33 in