10.2.4. Output choke (L2) - Models with parallel connection 400 kW ... 1.65 MW
The use of output chokes is mandatory for for parallel units; as a function of the application/connection, according to the follow-
ing criteria:
• for applications with short motor cables (≤ 100 m long) bus bars with an integrated ferrites (see Table 1) or Only Ferrites
may be used (see Table 2) or single distributor chokes may be used (see Table 3);
• for applications with long motor cables (> 100 m long) output choke may be used (see Table 4);
APPENDICE • Accessories & Options
Table 1: Busbars with integrated distribution chokes (Motor cable lenght distance ≤ 100 m)
Size Output Choke Current Current Model Code
inverter rating rating saturation
ADV200-4 ADV200-DC ADV200-6 ADV100 AFE200
[µH] [A] [A]
ADV200-4
400 kW HD / LD OUT-PW-KIT 2P S72641 l l
500 kW HD / LD OUT-PW-KIT 2P S72641 l l
630 kW HD / LD OUT-PW-KIT 2P S72641 l l
710 kW HD / LD OUT-PW-KIT 2P S72641 l l
900 kW HD / LD OUT-PW-KIT 3P S726411 l l
1 MW HD / LD OUT-PW-KIT 3P S726411 l l
ADV200-6
400 kW HD / LD OUT-PW-KIT 2P-690V S726412 l
500 kW HD / LD OUT-PW-KIT 2P-690V S726412 l
630 kW HD / LD OUT-PW-KIT 2P-690V S726412 l
710 kW HD / LD OUT-PW-KIT 2P-690V S726412 l
900 kW HD / LD OUT-PW-KIT 3P-690V S726413 l
1 MW HD / LD OUT-PW-KIT 3P-690V S726413 l
1,35 MW Not applicable
1,65 MW Not applicable