152 Inverter System & Power Supply Unit
Size Output inverter Choke rating [mH] Current rating [A] Current saturation [A] Model Code Dimensions (WxWxd, mm) and weight ADV200-4 ADV200-6 SMB200
APPENDICE • Accessories & Options
ADV100 ADV80 AFE200 FFE200
SMB200-D-1600-6+PRC 0.02 1443 2755 LR3-6-SMB-1600 S7ALF26 460 x 600 x 560; 210 kg l
SMB200-D-2500-6+PRC 0.013 2255 4305 LR3-6-SMB-2500 S7ALF27 480 x 720 x 370; 270 kg l
SMB200 (Pre-charge choke) (4)
SMB200-...-4 (380 ... 500 Vac) 0.1 70 400 LR3-4-PRC S7ALF10 180 x 165 x 140; 8 kg l
SMB200-...-6 (500 ... 690 Vac) 0.2 70 400 LR3-6-PRC S7ALF11 180 x 165 x 170; 15 kg l
(1) Integrated choke on DC-Link
(2) To reduce the line current THD even more (< 35%), use DC chokes wired between terminals C1 and C.
(3) Please refer to section "7.3 Standard connections" on page 112.
(4) Note: one precharge inductance only is required for parallel modules.